Vertiv | Liebert® GXT5 | Installer/User Guide 77
Chapter 7: Specifications
Table 7-1 UPS Specifications, 5-kVA to 10-kVA models
MODEL GXT5- 5000HVRT5UXLN 8000HVRT5UXLN 10KHVRT5UXLN
RATING 5000 VA/5000 W 8000 VA/8000 W 10000 VA/10000 W
Dimensions, D×W×H, in. (mm)
Unit 430×630×217 (16�9×24�8×8�5)
Shipping 646×816×520 (25�4×32�1×20�5)
Weight, lb.(kg)
Unit 71�1 (156�7) 75�5 (166�4)
Shipping 92(202�8) 94 (207�2)
Input AC
Operating Frequency, Nom� 50 or 60 Hz (factory-default is 60 Hz)
Factory-default VAC 208 VAC
User-configurable VAC
200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)
Operating voltage range
without battery operation
176 – 288 VAC (100 – 176VAC with power derating)
Maximum Allowable VAC 288 VAC
Input Frequency without Battery Operation 40 – 70 Hz
Input Power Connection PD5-CE6HDWRMBSU PD5-CE10HDWRMBSU
Output AC
AC-AC Eiciency 94% 95%
Factory-default VAC Frequency 208 VAC, 60 Hz
Output Power Connection PD5-CE6HDWRMBSU PD5-CE10HDWRMBSU
Waveform Sinewave
Normal Mode Overload
> 150% minimum 200 mS
125 – 150% for 60 seconds
105 – 125% for 5 minutes
≤ 105% continuous
Internal Battery Charger
Charger Current, A 2�25 A default, maximum 5 A 2�25 A default, maximum 8 A
Battery Parameters
Type Valve-regulated, non-spillable, flame-retardant, lead acid
Quantity x Voltage x Rating 16 x 12V x 9�0AH
Battery Mfr�/Part # LEOCH DJW12-9�0
Back-up time See Battery Run Times on page 81�
Upper-limit selections +10%, +15%, +20%; default +10%�
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation