29
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
76
TEST/EQ HRS = ##
or
TEST/EQ MAN STOP
or
END TEQ ##.##HRS
Configure
Menu
Displays the timed test/equalize
setting (and indicates the manually
initiated timed test/equalize feature
is enabled).
## = current setting for the manually
initiated timed test/equalize feature
(1-99).
or
If the "TEST/EQ HRS = ##" value is
increased above 99, "TEST/EQ MAN
STOP" is displayed to indicate the
manually initiated timed
test/equalize feature is disabled and
the system must be manually
returned to the float mode if placed
in the test/equalize mode.
or
If manually initiated timed
test/equalize feature is enabled and
the system is placed in the
test/equalize mode (via the MCA
interface), remaining test/equalize
time is displayed.
Note:
When "TEST/EQ MAN STOP"
or "END TEQ ##.##HRS" is
being displayed, press and
release the ALARM CUTOFF
and FUNCTION SET ENTER
pushbuttons simultaneously
to change the "TEST/EQ
HRS = ##" setting.
Yes, see
"System
Operating
Procedures".
76A
AUTO EQ DISABLED
or
AUTO EQ MUL = ##
or
END AUTO ##.## HR
Configure
Menu
Indicates the auto test/equalize
feature is disabled.
or
Displays the auto test/equalize
multiplier value.
or
Displays remaining auto
test/equalize time.
Yes, see
"System
Operating
Procedures".

Table of Contents