Vertiv | +24 VDC Power System User Manual (Section 6013) | Rev. G
40
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
130
PCU** ON: SET OFF
or
PCU** OFF: SET ON
or
Energy Mgmt. On
PCU
Enable Menu
Set Rectifier Module (PCU) On/Off
(Local TR Feature) - allows inhibiting
operation of specified PCU (Rectifier
Module).
The first Rectifier Module (PCU) is
displayed. Press the FUNCTION
SELECT UP or DOWN arrow
pushbutton to display the next or
previous, respectively, Rectifier
Module (PCU). Press the ALARM
CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously
to change the TR setting for this
Rectifier Module (PCU). At the "ARE
YOU SURE? + -" prompt, press either
the FUNCTION SET YES (+)
pushbutton to accept the new
setting, or the FUNCTION SET NO (-
) pushbutton to cancel this operation
without changing the existing
setting.
** = the designation of the Rectifier
Module (PCU).
Rectifier Modules (PCUs) cannot be
turned on or off if energy
management is active.
Yes, see
"System
Operating
Procedures".
131 CONFIGURE MENU
PCU
Enable Menu
Moves you back to this menu. No
132 NORMAL DISPLAY
PCU
Enable Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No
133-152 "Startup"
Startup
Sequence
Startup, see "Initially Starting the
System" in the separate Installation
Instructions (Section 6012).