Vertiv | +24 VDC Power System User Manual (Section 6013) | Rev. G
1.
Refer to description of the MAJOR alarm indicator for alarm conditions.
2.
Refer to description of the MINOR alarm indicator for alarm conditions.
3.
Activates if system output voltage increases to a preset adjustable value.
or
Test/Equalize Mode Indication 2:
Activates if the system is placed in the test/equalize mode, locally or
remotely.
4.
Activates if system output voltage increases to a preset adjustable value.
or
Rectifier Module Fail Major Alarm:
Activates if the Rectifier Module Fail alarm on two or more Rectifier
Modules is active. Refer to description of Rectifier Module Fail indicator for alarm conditions.
Activates if the MCA Fail alarm is active. Refer to description of MCA Fail alarm for
alarm conditions.
Activates if any fuse or circuit breaker in the system opens.
5.
Battery On Discharge Alarm:
Activates if system output voltage decreases to a preset adjustable
value, indicating that the battery is supplying the load and is discharging.
6.
50% Battery On Discharge or Very Low Voltage Alarm:
Activates if system output voltage decreases
to a preset adjustable value, indicating that the battery has been continuously supplying the load and
has discharged to approximately half its reserve time.
Activates if the AC Fail Alarm activates on two or more Rectifier Modules. Refer
to description of AC Fail Alarm for alarm conditions.
or
Rectifier Module Fail Minor Alarm:
Activates if the Rectifier Module Fail alarm on only one Rectifier
Module is active. Refer to description of Rectifier Module Fail indicator for alarm conditions.
7.
Activates if AC input drops below the low AC input voltage inhibit or increases above
the high AC input voltage inhibit..
8.
Activates if any alarm condition monitored by the MCA occurs, and is provided for
connection to an audible alarm circuit.
Activates if any fuse or circuit breaker in the system opens.
Activates if any LVD circuit in the system activates.
9.
Test/Equalize Mode Indication:
Activates if the system is placed in the test/equalize mode, locally or
remotely.
Activates if any fuse or circuit breaker in the system opens.
Rectifier Module Fail Alarm:
Activates if the Rectifier Module Fail alarm on any Rectifier Module is
active. Refer to description of Rectifier Module Fail indicator for alarm conditions.