48
Direct AC Input Connections to 588705400 List 03 Module Mounting Assemblies
Refer to Figure 23.
Figure 23:
Nominal 208 VAC / 240 VAC Input Connections (Three-Phase) to a 588705400 List 03 Module
Mounting Assembly
Rectifier
AC input connections are made using
the supplied
AC input line cords connected here.
Rear
Rectifiers are numbered left to
right as viewed from the front.
AC Input for
Rectifier Positions
#1, #2, #3
Rear
AC Input for
Rectifier Positions
#4, #5, #6
Input Connections are
Made using the Ordered
Input Line Cords
White*
Black*
Red*
Green*
L1
L2
L3
Ground
* Color of Input Line Cord Lead
Module Input Connector
(Cabinet Rear View)
AC Input
Line Cords
P/N 562046
Rectifier AC Input
(208 VAC / 240 VAC, Three Phase, 50 A)
P/N 562046
Plug End
Terminal G
(Green Wire)
Terminal Z
(Red Wire)
Terminal X
(Black Wire)
Terminal Y
(White Wire)
M4 Frame
Ground Screw
M4 Frame
Ground Screw

Table of Contents

Other manuals for Vertiv NetSure 7100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 7100 Series and is the answer not in the manual?

Vertiv NetSure 7100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 7100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals