VESDA-EVEP-A00-P Product Guide
72 www.xtralis.com
Parameter Default Values Range Affected by Return to
Factory Defaults
command
Minimum Maximum
Delays 10 seconds 0 seconds 60 seconds Yes
Cumulative Delay Unchecked Unchecked Checked Yes
Instant Fire Unchecked Unchecked Checked Yes
Significant Smoke
Change Logging
0.005 % obs/m
(0.0016 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
Yes
Significant Smoke
Change - VESDAnet
0.005 % obs/m
(0.0016 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
Yes
Work Days Monday through
Friday
n/a n/a Yes
Day Night Changeover Time
l Enabled Unchecked Unchecked Checked Yes
l Day Start 7 AM n/a n/a Yes
l Night Start 7 PM n/a n/a Yes
Holidays
l Enabled Unchecked Unchecked Checked Yes
l Start Holiday
Date
Blank n/a n/a Yes
l End Holiday Date Blank n/a n/a Yes
Air Flow
Air flow thresholds
l Major High 130% 105% 200% Yes
l Minor High 120% 105% 200% Yes
l Minor Low 80% 25% 95% Yes
l Major Low 70% 25% 95% Yes
Delay 30 seconds 15 seconds 250 seconds Yes
Significant Flow
Change
2.0 L/min 0.5 L/min 5 L/min Yes
Pipes in Use All pipes in use No pipes in use All pipes in use Yes
5
Aspirator Speed Setting 1 Setting 1 Setting 5 Yes
6
Filter
Service Interval 731 days 1 day 3655 days Yes
Referencing
Referencing Enabled Unchecked Unchecked Checked Yes
Detector Blank Zone 1 Zone 254 Yes
Delay 2 minutes 0 minutes 15 minutes Yes
Dilution Factor 100% 1% 100% Yes
General Purpose Inputs
GPI Function
(Unmonitored)
Reset n/a n/a Yes
Table5-4: Default Settings (continued...)