VESDA-EVES-A00-P Product Guide
54 www.xtralis.com
Command Description Execute From
A button
on the
Detector
Xtralis VSC
Software
Start AutoLearn Flow Starts the AutoLearn Flow process for the detector.
The detector monitors the environment and
determines appropriate airflow fault thresholds. The
user is prompted to enter the monitoring period.
When the AutoLearn has finished, the flow
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 75 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LEDstarts flashing
(approximately 15 seconds), then release the button.
Both Autolearn Smoke and Flow will run. The
monitoring period will be 14 days.
Cancel AutoLearn Flow Cancels the AutoLearn Flow process.
Flow thresholds will remain at levels set prior to
commencing AutoLearn Flow.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Start AutoLearn Smoke Starts the AutoLearn Smoke process for the
detector. The detector monitors the environment and
determines appropriate smoke thresholds. The user
is prompted to enter the monitoring period.
When the AutoLearn has finished, the smoke
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 75 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LEDstarts flashing
(approximately 15 seconds), then release the button.
Both Autolearn Smoke and Flow will run. The
monitoring period will be 14 days.
Cancel AutoLearn
Smoke
Cancels the AutoLearn Smoke process.
Smoke thresholds will remain at levels set prior to
commencing AutoLearn Smoke.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Table5-2: Detector Commands (continued...)