VESDA-EVES-A00-P Product Guide
www.xtralis.com 73
Parameter Default Values Range Affected by Return to
Factory Defaults
command
Minimum Maximum
Air Flow - Valve Test Do every 7
th
day Do every day Do every 7
th
day Yes
Pipes in Use All pipes in use No pipes in use All pipes in use Yes
Aspirator Speed Setting 1 Setting 1 Setting 10 Yes
Filter
Service Interval 731 days 1 day 3655 days Yes
Sector Name
Sector Name – Sector
Number 1 through 4
Blank n/a n/a Yes
Referencing
Referencing Enabled Unchecked Unchecked Checked Yes
Detector Blank Zone 1 Zone 254 Yes
Delay 2 minutes 0 minutes 15 minutes Yes
Dilution Factor 100% 1% 100% Yes
General Purpose Inputs
GPI Function
(Unmonitored)
Reset n/a n/a Yes
GPI Function
(Monitored)
Mains OK n/a n/a Yes
Button Lockout Unchecked Unchecked Checked Yes
Relays
Assignment of Relays
to conditions
See Table4-2 n/a n/a Yes
Normally Energized See Table4-2 n/a n/a Yes
Latching Checked Unchecked Checked Yes
Beep Unchecked Unchecked Checked Yes
AutoLearn Smoke and Flow Commands
Duration 14 days 15 minutes 16 days n/a
Table5-4: Default Settings (continued...)
1
The Xtralis VSC software forces the user to move the detector to a valid zone number.
2
The user must set the password the first time. There is no default password.
3
Default value set in factory. Not modified by return to factory defaults command.
4
The WiFi Security Key type depends on th e WiFi security method in use.