Why is my Victron Energy Inverter alarm LED flashing?
- DDoris LinSep 10, 2025
The alarm LED may flash for several reasons: * The DC input voltage is low, so you should charge the battery or check the battery connections. * The ambient temperature is too high, so you should place the inverter in a cool and well-ventilated room or reduce the load. * The load on the inverter is higher than the nominal load, so you should reduce the load. * Voltage ripple on the DC input exceeds 1.25Vrms, so you should check the battery cables and terminals and the battery capacity (increase if necessary). * Low battery voltage and excessive load, so you should charge the batteries, reduce the load, install batteries with a higher capacity and use shorter and/or thicker battery cables.