4000 Series
Art.4312 - Installation instructions
SYSTEM SETTINGS
System par. menu Parameter Name Programming method Permission Default value
1: Test connection / / / /
2: Language Language By panel and PC software Only Engineer English
3: ID ID By panel and PC software Only Engineer 1
4: Panel mode Panel mode By panel and PC software Only Engineer Local
Security Level Only by PC software / Fob or Code
Mode Only by PC software / Compatibility mode
Enable Direct Call Only by PC software / Disabled
Proximity Access Mode Only by PC software / Stand alone mode
LANGUAGE
Languages supported are: English, Italian, Spanish, Portuguese,
French, German, Czech, Croatian, Danish, Polish, Slovenian,
Dutch and Hebrew.
Only user messages change language, the programming menu’s
are always in English.
Modify routine
• press 2 to enter into edit mode
• press 2 repeatedly to scroll through the available languages
• press
to save or to exit edit mode without saving.
SECURITY LEVEL
Art.4312 can work in two dierent security modes: Fob or Code
and Fob + Code.
In Fob or Code, key and code are linked only with user. Insertion of
enabled code or passing a key over the reader will open the door.
In Fob + Code, key and code are linked together. Single code is
linked with single key. A user must enter a code and present a
key to open the door. Parameter can be changed only through
PC programming routine.
ID
The panel ID came be from 1 to 15. Each panel on a system
should have a unique ID.
Modify routine
• press 3 to enter into edit mode
• Enter the panel ID from 1 to 15
• press
to save or to delete characters or exit edit mode
without saving.
MODE
Options are COMPATIBILY MODE or NORMAL MODE.
COMPATIBILITY MODE guarantees retro compatibility with older
programming interfaces but restricts the features of the panel.
NORMAL MODE enables features of oor eld in user item,
multiple code-to-user or key-to-user linking. This means that
user can manage more than one open door code and key.
In COMPATIBILITY MODE each user only has one access code.
PANEL MODE
Species whether or not the system includes the block ex-
changer Art.2306.
If there are no Art. 2306 in the system, this setting MUST be
LOCAL (panel ID between 1 and 15).
If they are present and the panel is connected on the MAIN BUS
of Art.2306 (BUS-M), this setting must be MAIN (panel ID be-
tween 9 and 15): the outdoor panel can call any indoor station
connected to any block exchanger.
If the panel is connected to the LOCAL BUS of Art.2306 (BUS-L),
this setting must be LOCAL (panel ID between 1 and 8): it will
only call the indoor stations connected to the output (BUS-O)
of that block.
Modify routine
• press 4 to enter into edit mode
• press 4 to switch from LOCAL to MAIN and vice versa
• press
to save or to exit edit mode without saving.
ENABLE DIRECT CALL
It species whether Direct Call Mode is active or not. If yes, only
the rst 18 or 15 (depending on keyboard conguration) users
written in memory are active. Pushing the rst key from top left
corner of keyboard will call rst user memory location.
PROXIMITY ACCESS MODE
This parameter species if the proximity reader works in a self
contained standalone mode or is connected via a Wiegand in-
terface to an external controller such as Portal Plus.
STANDALONE MODE: when a fob/code is used the panels in-
ternal memory is checked for a match. If a match is found the
relay will energise and the display will show the door opening. If
no match is found the display will show NOT FOUND.
WIEGAND MODE: When a fob/code is used the panel sends
the data to the Wiegand output and awaits a reply. If the ex-
ternal Wiegand controller replies by setting the LR terminal to
0V then the fob/code is denied and the display will show NOT
ALLOWED. If the external Wiegand controller replies by setting
the LG terminal to 0V then the key is accepted and the display
will show door open. If the Wiegand control does not reply then
the panel will show NOT FOUND.
Art.4312 Audio/video digital front panel