Selection diagrams, cylinder loading system Vitocell 100-L, type CVLA, with Vitotrans 222
Performance factor N
L
CA B
500 l
950 l
750 l
1900 (2 x 950) l
2850 (3 x 950) l
1500 (2 x 750) l
20
10
40
60
240
220
200
180
160
140
120
100
80
0
50
100
150
200
Heating output in kW
Performance factor NL
250
300
A
Vitotrans 222, up to 80 kW
B
Vitotrans 222, up to 120 kW
C
Vitotrans 222, up to 240 kW
Information on performance factor N
L
The performance factor N
L
depends on the cylinder storage temper-
ature T
cyl
.
Standard values
T
cyl
= 60 °C → 1.0 × N
L
T
cyl
= 55 °C → 0.75 × N
L
T
cyl
= 50 °C → 0.55 × N
L
T
cyl
= 45 °C → 0.3 × N
L
Peak output (over 10 minutes)
1500 (2 x 750) l
20
0
40
60
240
220
200
180
160
140
120
100
1000
Heating output in kW
Peak output in l/10min
500
0
1500
2000
2500
3000
80
500 l
950 l
750 l
1900 (2 x 950) l
2850 (3 x 950) l
CA B
A
Vitotrans 222, up to 80 kW
B
Vitotrans 222, up to 120 kW
C
Vitotrans 222, up to 240 kW
Information regarding peak output
The peak output during a 10 minute period depends on the cylinder
storage temperature T
cyl
.
Standard values
T
cyl
= 60 °C → 1.0 × peak output
T
cyl
= 55 °C → 0.75 × peak output
T
cyl
= 50 °C → 0.55 × peak output
T
cyl
= 45 °C → 0.3 × peak output
Selecting the cylinder type
(cont.)
12
VIESMANN
DHW heating