EasyManua.ls Logo

Viessmann Vitoclima 200-C - Placing the Unit in Standby Mode; Ensuring that Load Is Drawn; Switching the Unit on

Viessmann Vitoclima 200-C
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Placing the unit in standby mode
!
Please note
Starting the compressor in a
cold state can result in equip-
ment damage.
Prior to commissioning, leave
the unit at least 4 hours in
standby mode.
Only commission the unit when
the lower part of the compres-
sor is at least warm to the
touch.
1. Start the unit with the ON/OFF
switch (B in the Fig. on page 6 or
A in the Fig. on page 8)
The return temperature is dis-
played on the programming unit.
2. The following only applies if a
dot is shown in the segmented
display:
The unit is in standby mode.
Leave the unit in this state for
approx. 4 h.
3. The following only applies if fig-
ures are shown in the segmented
display:
Press D (see page 27).
A dot appears in the programming
unit display. The unit is in standby
mode.
Leave the unit in this state for
approx. 4 h.
Ensuring that load is drawn
Prior to switching the unit ON, ensure
a load of at least 60 % of the rated
output is drawn, in the respective
operating mode (heating/cooling).
For this, fully open the valves in the
heating or cooling circuit as well as
any other control elements that may
be installed.
Switching the unit ON
!
Please note
Starting the compressor in a
cold state can result in equip-
ment damage.
Prior to commissioning, the
unit must have been in standby
mode for at least 4 h.
Only commission the unit when
the oil sump of the compressor
is at least warm to the touch.
!
Please note
A sudden change from heating
to cooling mode can result in
high pressure faults.
Prior to a changeover, the
return temperature must have
fallen below 25 °C.
1. Press D.
The programming unit display
shows the return temperature.
Further details regarding the individual steps (cont.)
17
Commissioning, inspection, maintenance
5692 696 GB

Table of Contents