Heating operation
*
1
*
2
Return temperature (HEA): max. 45.0 °C (standard setting 40.0 °C)
Flow temperature: Return temperature plus 5 to 8 K
Cooling operation
*
3
Return temperature (Coo): approx. 12.0 °C (standard setting 12.0 °C)
Flow temperature: Return temperature less 5 to 8 K
Checking the superheating and correcting, if required
(cooling mode)
The unit is equipped with a thermostatic expansion valve with external pressure
compensation. At the factory, the expansion valve is set to 5 K superheating.
Checking the superheating
To ensure adequately accurate test
values, start the unit at least 5 min-
utes before the test is started.
1. Determine the low pressure with
the pressure gauge attached to the
inlet side of the service valve (see
Fig. on page 7 and 8).
2. Using the temperature scale of the
pressure gauge, determine the
saturation temperature of the inlet
side (Tse) that corresponds to this
pressure.
3. Place a contact thermometer at the
outlet connector of the evaporator
and determine the effective tem-
perature (Tsa).
4. Calculate superheating S from
Tse Tsa.
5. Record the determined values in
the service report from page 46.
Adjusting the superheating
1. Rotate the adjusting screw of the
thermostatic expansion valve by up
to ½ turn.
2. Let the unit run for at least 5 min.
3. Recheck the superheating.
4. If required, repeat steps 1 to 3.
Note
Should the thermostatic expansion
valve fail to respond to the superheat-
ing adjustment, it may be stuck or
faulty and may need to be replaced.
Further details regarding the individual steps (cont.)
22
Commissioning, inspection, maintenance
5692 696 GB
*1
Relative to an outside temperature of 7 °C.
*2
Only for type OC...H (heat pump versions).
*3
Relative to an outside temperature of 35 °C.