Press the following keys:
1. D press until parameter
"PSS" is displayed.
2. CD simultaneously for less
than 2 s; the display
shows " ".
3. C press until value "177" is
displayed.
4. CD simultaneously and for at
least 5 s; the code entry
is saved and the next
higher menu level is dis-
played.
5. To return to the standard display
(return temperature), repeat step 4.
Selecting the set value for heating mode (HEA)
Press the following keys:
1. CD simultaneously and
briefly (< 2 s); the display
shows "SET".
2. CD simultaneously and
briefly; the display shows
"Coo".
3. D the display shows
"HEA".
4. CD simultaneously and
briefly; the display shows
the current set value.
5. C to raise the set value
or
6. D to lower the set value
7. CD simultaneously and for at
least 5 s; the change is
saved and the next
higher menu level is dis-
played.
8. To return to the standard display
(return temperature), repeat step 7
several times.
Standard setting 40 °C
Setting range 35 to 44 °C