Code Description Possible cause Measures
E41 Flow limiter Inadequate throughput in-
side the hydraulic circuit
Note
The message is automati-
cally acknowledged until
three fault messages in
one hour occur for the first
time.
Check differential pressure
switch, circulation pump and
water filter
Diagnosis
Diagnosis without display on the control unit
Fault Possible cause Measures
Unit operates con-
stantly but without
cooling effect
Inadequate refrigerant fill-
ing
Top up refrigerant
Filter dryer blocked Replace the filter dryer
Ice on the suction
line
The preselected super-
heating is incorrect
Increase the superheating
setting
Check refrigerant level
Increased noise
development
Lines vibrating Check line retainers (if in-
stalled)
Thermostatic expansion
valve hisses
Top up refrigerant
Check filter dryer
Compressor noisy Check compressor mounts
Compressor bearing worn;
replace compressor
Low oil level inside
the compressor
One or several refrigerant
or oil leaks in the refriger-
ant circuit
Identify and repair leaks
Mechanical compressor
damage
Check compressor and re-
place, if required
Oil sump heater faulty Check oil sump heater and
replace, if required