Vitoclima 200-C Type OC208 OC211
Rated cooling capacity
kW 8.1 10.5
Power consumption (compressor) kW 3.0 3.2
Performance factor (EER) (com-
pressor)
2.5 3.3
Flow rate (min./max.) l/h 1162/1742 1505/2258
Electrical values
Power supply 3/N/PE 400 V/50 Hz
Rated current (only compressor) A 5.8 6.2
Starting current (only compres-
sor)
A 36 50
Max. power consumption
*
1
kW 4.6 4.7
Power consumption, oil sump
heater
W 70 70
Power consumption, secondary
heat exchanger heater
W 35 30
Refrigerant circuit
Process medium R 407 C
Fill volume kg 2.0 2.42
Compressor Type Scroll
Surface area (W x H) primary
heat exchanger
mm 640 x 810 1200 x 890
Fans
No. 1 2
Air flow rate m
3
/h 2800 5600
Speed rpm 800 800
max. power consumption kW 0.15 0.3
Noise specification
Sound power level dB(A) 67 69
Sound pressure level
*
2
dB(A) 36 38
Dimensions and weight
Total length mm 400 400
Total width mm 1182 1182
Total height mm 905 1309
Weight kg 110 153
Permissible operating pressure bar 3.0 3.0
Hydraulic
Flow connection R 1" 1"
Return connection R 1" 1"
Diaphragm expansion vessel (ca-
pacity)
l 2 5