Press the following keys:
1. CD simultaneously and
briefly (< 2 s); the display
shows "SET".
2. CD simultaneously and
briefly; the display shows
"Coo".
3. CD simultaneously and
briefly; the display shows
the current set value.
4. C to raise the set value
or
5. D to lower the set value
6. CD simultaneously and for at
least 5 s; the change is
saved and the next
higher menu level is dis-
played.
7. To return to the standard display
(return temperature), repeat step 6
several times.
Standard setting 12 °C
Setting range 10 to 15 °C
Scanning sensor values
Press the following keys:
1. CD simultaneously and
briefly (< 2 s); the dis-
play shows "SET".
2. D to display "tP".
3. CD simultaneously and
briefly; the display
shows "T01".
4. CD simultaneously and
briefly; the display
shows the temperature
at the return tempera-
ture sensor (ST1).
5. CD simultaneously and at
least for 5 s; the display
shows "T01".
6. D to display "T02".
7. CD simultaneously and
briefly; the display
shows the temperature
at the flow tempera-
ture sensor (ST2).
8. CD simultaneously and at
least for 5 s; the display
shows "T02" again.
9. D to display "T03".
10. CD simultaneously and
briefly; the display
shows the temperature
at the air heat exchan-
ger sensor (ST3).
Selecting the set value for cooling mode (Coo)
37
Control settings
5692 696 GB