Changing slope and level
A Changing the slope
B Changing the level
1. Change the slope with coding
address "d3" in code 1 (see
page 38).
Adjustable value 2 to 35 (equals
slope 0.2 to 3.5).
2. Change the level with coding
address "d4" in code 1 (see
page 38).
Adjustable value from -13 to +40 K.
Adjusting the set room temperature
Standard room temperature:
1. In case of two heating circuits –
select the relevant one:
&
Press a.
&
"1r" flashes on the display.
&
Select heating circuit A1 (heating
circuit without mixer):
&
Press d.
&
Select heating circuit with mixer
M2:
– – Press a.
– – "2r" flashes on the display.
– – Press d.
Further details regarding the individual steps (cont.)
34
Initial start-up, inspection, maintenance
5692 536 GB