Vitotrol 200A, Installation, Operating and Service
5583 141 v1.0
4
Location
Installation
H Operation with room temperature dependent control
– On an internal wall in the living space, at a height
of approximately 5 ft. (1.5 m) from the floor
– Not near windows and doors
– Not above radiators
– Not near heat sources (direct sunlight, fireplace,
TV set etc.
Do not install further controllers in this room. Open any
thermostatic radiator valves fully.
The remote unit contains a built-in room temperature
sensor, which measures the room temperature.
The Room Temperature Sensor can only be used for room
temperature sensing in the main living area, adjusting the
boiler water temperature or supply temperature to the
individual room. The room temperature sensor does not
have any adjustment possibilities. Adjustments related
to the room temperature must be performed on the
programming unit of the control or on the remote control.
Thermostat valves of the radiators located in the same
room as the Room Temperature Sensor must be open at
all times.