Configuring the Remote Control
Commissioning
Changing the Configuration During the Operation
Up to 2 remote controls may be connected to the boiler
control unit.
1. Switch ON the power supply on the control unit.
The remote control display shows “H 1”.
2. With
select heating circuit 1 (“H 1”), heating
circuit (“H 2”) or heating circuit (“H 3”).
3. OK as confirmation. The operating state of the
heating system is transferred. Rotate the display
segments (this may take up to 5 min).
1. Press
and simultaneously at the remote control
for approx. 4 sec.
2. With select heating circuit 1 (“H 1”), heating
circuit (“H 2”) or heating circuit (“H 3”).
3. OK as confirmation.
The operating state of the heating system is
transferred.
Rotate the display segments (this may take up to
5 min).
Note: If the heating circuit assignment is later cancelled,
reset coding address A0 for this heating circuit at
the control unit to 0 (fault message bC, bd, bE).