Fault diagnosis
Fault Possible cause Fault rectification
Urinal flushing
constantly
Solenoid valve not
operating correctly
•
Make sure that the connected
water line is opened only after
the urinal control system has
been started for a minimum of
30 seconds (make the power
connection).
•
Make sure that the solenoid valve
is connected to the controller.
•
Check cable connection.
•
Check the functioning of the
solenoid valve (diagnostics mode,
see separate operating instructions
or check via app).
•
Make sure that the solenoid valve
is integrated in the water circuit
with the correct flow direction
(marked on the valve housing).
EN
S. 77