12
SW24.W
EN
OUT
Auxiliary output conguration
19
Electric lock
Default
1
OFF Output o
1 Electrical solenoid lock
2 Electrical drop lock
3 Electrical magnetic lock (suction) on in closing
4 Electrical magnetic lock (suction) on in opening and closing
19T
Electrical solenoid lock excitation time
(adjustable at intervals of 0.1 s)
Default
1.2
0.5 0.5 s (minimum time)
5.0 5.0 s (maximum time)
A1
Terminal A1 output type
Default
1
OFF Output o
1
Gate open warning light (SCA)
Operation as per SCA parameter setting
2
Auxiliary Radio output (RAU)
Operation as per RAU parameter setting
3
Courtesy light (LCO)
On during leaf movement and for the amount of time after the leaf stopping set in parameter
LCO
4
Zone light (LZO)
On during leaf movement
5
Gate left open (OAB)
On if the gate remains open for a time longer than that dened by the open gate alarm logic
(L16)
6
Maintenance (MAN)
Output o when the number of maintenance signalling manoeuvres (MNPS) is reached in
the diagnostics section
A2
Terminal A2 output type
Default
2
OFF Output o
1
Gate open warning light (SCA)
Operation as per SCA parameter setting
2
Auxiliary Radio output (RAU)
Operation as per RAU parameter setting
3
Courtesy light (LCO)
On during leaf movement and for the amount of time after the leaf stopping set in parameter
LCO
4
Zone light (LZO)
On during leaf movement
5
Gate left open (OAB)
On if the gate remains open for a time longer than that dened by the open gate alarm logic
(L16)
6
Maintenance (MAN)
Output o when the number of maintenance signalling manoeuvres (MNPS) is reached in
the diagnostics section
7
Synchronization output, compass type interlock (INB)
Automatically congures input S4 as synchronization input without any choice by the user.
The control panel consents to the gate opening only if the other gate is in the closed posi-
tion
8
Synchronization output, compass type interlock (INP) with presence signal.
Automatically congures input S4 as synchronization input and S3 as presence input with-
out any choice by the user.
The control panel consents to the gate opening only if the other gate is in the closed posi-
tion and the presence input is occupied