Manual VIPA System SLIO Chapter 4 Analog Input
HB300E - SM - Rev. 09/38 4-29
Depending on the Interference frequency suppression for each channel the
transducer velocity may be set.
Code Velocity/channel at Interference frequency suppression
50Hz 60Hz
00h 324.1 270.5
01h 164.2 137.2
02h 84.2 70.5
03h 44.1 37.2
04h 24.2 20.5
05h 14.2 12.2
06h 9.2 8.0
07h 6.6 5.9
08h 4.2 3.8
For each channel an upper and a lower limit may be defined. As soon as
the measuring value is be beyond the limits and the limit value monitoring is
activated, a process interrupt is initialized.
In the following there are the measuring ranges with function-number listed,
which were supported by the analog module. With FFh the corresponding
channel is deactivated.
Function option
Upper limit value
Lower limit value
Function-number
channel x