Manual VIPA System 300V Chapter 3 Profibus DP
HB130E - IM - Rev. 08/26 3-17
Diagnostic data consists of:
• Standard diagnostic data (Byte 0 ... 5)
• Identifier-related diagnostic data (Byte 6 ... 10)
• Module-related diagnostic data (Byte 11 ... 22)
• Channel-related diagnostic data (Byte 23 ... 25)
Standard diagnostic data
Byte 0 Station state 1
Byte 1 Station state 2
Byte 2 Station state 3
Byte 3 Master address
Byte 4 Ident number (low)
Byte 5 Ident number (high)
Identifier-related diagnostic data
Byte 6 Length and code identifier-related diagnostic
Byte 7 ... Byte 10 Identifier-related diagnostic messages
Module-related diagnostic data
Byte 11 Length and code module-related diagnostic
Byte 12 Module state
Byte 13 ... Byte 14 0 (fix)
Byte 15 ... Byte 22 Module-related diagnostic messages
Channel-related diagnostic data
Byte 23 Ident number of the module
Byte 24 Number of the channel
Byte 25 Error code
Diagnostic data
IM 353-1DP00