EasyManua.ls Logo

VIPA System 300V - Chapter 3 Hardware Description; Components: LEDs and Interfaces

Default Icon
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual VIPA System 300V Chapter 3 Profibus DP
HB130E - IM - Rev. 08/26 3-17
Diagnostic data consists of:
Standard diagnostic data (Byte 0 ... 5)
Identifier-related diagnostic data (Byte 6 ... 10)
Module-related diagnostic data (Byte 11 ... 22)
Channel-related diagnostic data (Byte 23 ... 25)
Standard diagnostic data
Byte 0 Station state 1
Byte 1 Station state 2
Byte 2 Station state 3
Byte 3 Master address
Byte 4 Ident number (low)
Byte 5 Ident number (high)
Identifier-related diagnostic data
Byte 6 Length and code identifier-related diagnostic
Byte 7 ... Byte 10 Identifier-related diagnostic messages
Module-related diagnostic data
Byte 11 Length and code module-related diagnostic
Byte 12 Module state
Byte 13 ... Byte 14 0 (fix)
Byte 15 ... Byte 22 Module-related diagnostic messages
Channel-related diagnostic data
Byte 23 Ident number of the module
Byte 24 Number of the channel
Byte 25 Error code
Diagnostic data
IM 353-1DP00

Other manuals for VIPA System 300V

Related product manuals