Chapter 3 Profibus DP Manual VIPA System 300V
3-38 HB130E - IM - Rev. 08/26
Installation guidelines
The VIPA Profibus DP network must have a linear structure.
Profibus DP consists of minimum one segment with at least one master
and one slave.
A master is always used in conjunction with a CPU.
Profibus supports a max. of 125 participants.
A max. of 32 devices are permitted per segment.
The maximum length of a segment depends on the transfer rate :
9.6 ... 187.5kBaud 1000m
500kBaud 400m
1.5MBaud 200m
3 ... 12MBaud 100m
The network may have a maximum of 10 segments. Segments are
connected by means of repeaters. Every repeater is also seen as
participant on the network.
All devices communicate at the same baud rate, slaves adapt automa-
tically to the baud rate.
The bus must be terminated at both ends.
Masters and slaves may be installed in any combination.
Assemble your Profibus system using the required modules.
Transfer the supplied GSD-file into your system and configure the
system as required. Choose a valid Profibus address.
Transfer the configuration into your master.
Connect the Profibus cable to the coupler and turn the power supply on.
Profibus in