Manual VIPA System 300V Chapter 3 Profibus DP
HB130E - IM - Rev. 08/26 3-37
… continue
Interrupt status at diagnostic interrupt Bytes x+8 to x+19
(corresponds to CPU diagnostic record set 1)
Byte Bit 7 ... Bit 0
x+8 70h: Module with digital inputs
71h: Module with analog inputs
72h: Module with digital outputs
73h: Module with analog outputs
74h: Module with analog in-/-outputs
76h: Counter
x+9 Length of the channel-related diagnostic
x+10 Number of channels per module
x+11 Position (channel) with diagnostic event
x+12 Diagnostic event on the channel/channel group 0
Assignment see module description
x+13 Diagnostic event on the channel/channel group 1
Assignment see module description
.
.
.
.
.
.
x+19 Diagnostic event on the channel/channel group 7
Assignment see module description
Interrupt status at hardware interrupt Bytes x+4 to x+7
More detailed information to the diagnostic data is to find in the concerning
module descriptions.