Chapter 3 Profibus DP Manual VIPA System 300V
3-32 HB130E - IM - Rev. 08/26
Via the Identifier-related diagnostic you gain information at which plug-in
location (module) an error has occurred.
More detailed information about the error is available via the Module state
and the channel-related diagnostic.
The identifier-related diagnostic can be activated via the parameterization
and has the following structure:
Identifier-related diagnostic
Byte Bit 7 ... Bit 0
X Bit 5 ... 0: 000101 (fix) Length of the Identifier-related
diagnostic
Bit 7 ... 6: 01 (fix) Code for Identifier-related diagnostic
X+1 The bit is set if one of the following occurs:
- a module is removed
- an unconfigured module is inserted
- an inserted module cannot be accessed
- a module reports a diagnostic interrupt
Bit 0: Entry for module on slot 1
Bit 1: Entry for module on slot 2
Bit 2: Entry for module on slot 3
Bit 3: Entry for module on slot 4
Bit 4: Entry for module on slot 5
Bit 5: Entry for module on slot 6
Bit 6: Entry for module on slot 7
Bit 7: Entry for module on slot 8
X+2 Bit 0: Entry for module on slot 9
Bit 1: Entry for module on slot 10
Bit 2: Entry for module on slot 11
Bit 3: Entry for module on slot 12
Bit 4: Entry for module on slot 13
Bit 5: Entry for module on slot 14
Bit 6: Entry for module on slot 15
Bit 7: Entry for module on slot 16
X+3 Bit 0: Entry for module on slot 17
Bit 1: Entry for module on slot 18
Bit 2: Entry for module on slot 19
Bit 3: Entry for module on slot 20
Bit 4: Entry for module on slot 21
Bit 5: Entry for module on slot 22
Bit 6: Entry for module on slot 23
Bit 7: Entry for module on slot 24
X+4 Bit 0: Entry for module on slot 25
Bit 1: Entry for module on slot 26
Bit 2: Entry for module on slot 27
Bit 3: Entry for module on slot 28
Bit 4: Entry for module on slot 29
Bit 5: Entry for module on slot 30
Bit 6: Entry for module on slot 31
Bit 7: Entry for module on slot 32
Identifier-related
diagnostic