Chapter 4 CANopen Manual VIPA System 300V
4-8 HB130E - IM - Rev. 08/26
0
1
The address selector is used to specify the module-ID as well as the CAN
baud rate. Each module ID must be unique on the bus.
For details please refer to "IM 353CAN - CANopen slave - Baud rate and
module-ID" in this chapter.
The CAN-bus coupler is equipped with an internal power supply. This
power supply requires DC 24V. In addition to the internal circuitry of the
bus coupler the supply voltage is also used to power any modules
connected to the backplane bus. Please note that the maximum current
that the integrated power supply can deliver to the backplane bus is 3.5A.
The power supply is protected against reverse polarity.
CAN-Bus and backplane bus are isolated from each other.
Attention!
Please ensure that the polarity is correct when connecting the power
supply!