VMAC Vehicle Mounted Air Compressors
Toll Free: 1-800-738-8622 Local: 1-250-740-3200
Fax: 1-250-740-3201
15
HYD TEMP. SENSOR
Allows temporary over-ride of the hydraulic temperature probe.
This is only intended to be used in an emergency to
complete a job when servicing the unit is not
immediately possible. Running without a temperature
sensor may result in failure of the unit and/or damage to
the hydraulic system, and is not recommended.
To temporarily disable the temperature sensor, press and hold the
ON button for 2 seconds. The display will show:
NO HYD TEMP PRB?
Press and hold the ON button for 5 seconds. The display will show:
TEMP PROBE DIS
The air temperature sensor has been disabled.
If you press and hold the OFF button for 5 seconds, the display will
show:
TEMP PROBE EN
The air temperature sensor has been enabled.
SYSTEM PRESSURE
Allows adjustment of the maximum system pressure.
Range: 110 to 150 psi
Factory setting: 150 psi
Press and hold the ON button for 2 seconds. The display will show:
ADJ OFF PRES XXX
The XXX is the current pressure setting in psi. Scroll through the
range of settings. When the desired setting is displayed, exit
normally and the change will be made.
!