Release date 2016-09-13 11:47 Date of issue 2016-09-13 132964_eng.xml
Technical data KFD2-SR2-Ex2.W.SM
3
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage U
m
253 V AC (Attention! The rated voltage can be lower.)
Error message output
Maximum safe voltage U
m
40 V DC (Attention! U
m
is no rated voltage.)
Statement of conformity TÜV 99 ATEX 1493 X
Group, category, type of protection,
temperature class
¬ II 3G Ex nA nC IIC T4
Output
Contact loading 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0035
CSA approval
Control drawing 116-0047
IECEx approval IECEx PTB 11.0034
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.