EasyManuals Logo

VOKERA Excel 29 User Manual

VOKERA Excel 29
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
14
IMPORTANT
The vertical ue terminal is 1.0 metre in length and cannot be
cut; therefore it may be necessary to adjust the height of the
appliance to suit or use a suitable extension.
Connect the vertical ue assembly to the boiler ue spigot us-
ing the 100mm clip, gasket & screws (supplied), ensuring the
correct seal is made. The ue support bracket (supplied with
the vertical ue kit) can now be tted.
If the vertical ue requires extension/s or additional bend/s,
connect the required number of ue extensions or bends (up
to the maximum equivalent ue length) between the boiler and
vertical ue assembly (see g. 14).
Ensure that any horizontal sections of the ue system have a
minimum 1º; maximum 3º fall back to the boiler (1º = 17mm
per 1000mm).
NOTE
When cutting an extension to the required length, you must
ensure that the excess is cut from the plain end of the exten-
sion. Remove any burrs, and check that any seals are located
properly.
You must ensure that the entire ue system is properly sup-
ported and connected.
4.5.3 TWIN FLUE SYSTEM
The Vokèra twin ue system enables greater ue distances
to be achieved than that of a concentric ue system. It can be
used for horizontal or vertical applications, however the twin
ue system must be converted to the dedicated concentric
ue kit for termination. It is essential that the installation of the
twin ue system be carried out in strict accordance with these
instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
The ue must have a have a minimum 1º; maximum 3º (1º =
17mm per 1000mm) fall back to the appliance to allow any
condensate that may form in the ue system to drain via the
condensate drain. Consideration must also be given to the fact
that there is the possibility of a small amount of condensate
dripping from the terminal.
Ensure that the entire ue system is adequately supported,
use at least one bracket for each extension.
The entire ue system must be adequately insulated to
maintain heat within the ue system thereby reducing the
possibility of condensate production.
As the exhaust outlet pipe can reach very high temperatures
it must be protected to prevent persons touching the hot
surface.
The condensate drain pipe must be connected in accordance
with building regulations.
Reduction for bends
Twin ue accessories
Part No. Description Length
0225805 Horizontal ue terminal 1.0 metre
0225810 Vertical ue terminal 1.0 metre
359 Twin adapter kit N/A
531 Pitched roof ashing plate N/A
532 Flat roof ashing plate N/A
0225815 Condensate drain kit N/A
0225820 0.25m extension (pair) 250mm
0225825 0.5m extension (pair) 500mm
0225830 1.0m extension (pair) 1000mm
0225835 2.0m extension (pair) 2000mm
0225840 45º bend (pair) N/A
0225845 90º bend (pair) N/A
0225850 Twin bracket (5) N/A
0225855 Single bracket (5) N/A
MOUNTING THE BOILER
The xing holes for the wall-mounting bracket should now be
drilled and plugged, an appropriate type and quantity of xing
should be used to ensure that the bracket is mounted securely.
Fig. 13a
HORIZONTAL TERMINATION (g. 13c)
The twin ue system must be converted to the dedicated con-
centric ue kit for termination.
The horizontal terminal is supplied with a built-in converter
box and cannot be shortened.
A 130mm hole is required for the passage of the concentric
terminal through the wall.
The air inlet pipe must always be level with or below, that of
the exhaust pipe.
Depending on site conditions it may be preferable to install the
terminal assembly prior to tting the twin ue pipes.
Mark and drill a level 130mm hole for the passage of the horizontal
ue terminal. Insert the terminal assembly into the ue hole.
Push-t the twin ue pipes onto the concentric to twin converter
box ensuring that the exhaust pipe connects to the exhaust
connection on the concentric to twin converter.
If necessary cut the plain ends (male) of the twin ue pipes to
allow connection to the concentric to twin converter.
NOTE
Before cutting twin ue pipes ensure allowances have been
made for connection onto the previous piece and onto the con-
centric to twin converter. The last twin ue pipes must be pushed
50mm onto the male spigots of the concentric to twin converter.
NOTE
Seal the ue terminal assembly to the wall using cement or a
suitable alternative that will provide satisfactory weatherproof-
ing. The interior and exterior trim can now be tted.
VERTICAL TERMINATION (g. 14)
The twin ue system must be converted to the dedicated con-
centric ue kit for termination.
The vertical terminal is supplied with a built-in converter box
and cannot be shortened.
Once the bracket has been secured to the wall, mount the ap-
pliance onto the bracket.
INSTALLATION OF TWIN ADAPTOR KIT (g. 13a-13b)
Insert the exhaust connection manifold (A) onto the appliance
ue outlet.
Remove the blanking plate (located to the left of the appliance
ue outlet) and using the same screws install the air inlet
plate (B).
Using the hole in the exhaust connection manifold as a guide,
drill a 3mm hole in the appliance ue spigot and secure the
exhaust manifold connection to the ue spigot using the screw
provided (C).
Using the two holes in the air inlet plate as a guide, drill a
3mm hole in each and secure the air inlet pipe/bend using
the screws provided.
The twin ue pipes extensions and accessories can now be
installed by pushing together (the plain end of each extension
or bend should be pushed approximately 50mm into the female
socket of the previous piece).
B
A
C
Bend Reduction in maximum ue length for each bend
45º bend 1.0 metre
90º bend 1.5 metre
Fig. 13b

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the VOKERA Excel 29 and is the answer not in the manual?

VOKERA Excel 29 Specifications

General IconGeneral
ERP RatingA
Boiler TypeCombination
Output (kW)29 kW
MountingWall Mounted
DHW Output (kW)29 kW
Operating Pressure0.5 - 3 bar

Related product manuals