Holdfor3secondstoswitchCelsius(℃)andFahrenheit(℉)
6. Troubleshooting
6.1ErrorcodeontheLEDcontroller
Malfunction Code Reason Solution
Watertemperature
sensorfailure
P1
Watertemperaturesensoropen
circuitorshortcircuit.
1.Checkthesensorwiring.
2.Replacethenewwatertemperature
sensor.
Pipingtemperaturesensor
failure
P3
Pipingtemperaturesensoropen
circuitorshortcircuit.
1.Checkthesensorwiring.
2.Replacethenewpipingtemperature
sensor.
Ambienttemperature
sensorfailure
P5
Ambienttemperaturesensor
opencircuitorshortcircuit.
1.Checkthesensorwiring.
2.Replacethenewwatertemperature
sensor.
Toolowortoohigh
ambienttemperature
protection
E0
1.Ambienttemperatureisoutof
operatingrange:
23°F~109.4°F.
2.Controllerfailure.
1.Waittheambienttemperature
recovertheoperationrange.
2.Replacethenewcontroller.
Waterflowfailure E3
1.
Insufficientornowaterflow.
2.
Thewiringforwaterflow
switchisinloosesituation.
3.
Malfunctionofwaterflow
switch
1.
Checkthewaterpumporwater
pipingsystem.
2.
Checkthewiringofwaterflow
switch.
3.
Replaceanewwaterflowswitch