6. Trouble shooting
6.1 Error code on the LED controller
Water temperature
sensor failure
Water temperature sensor open
circuit or short circuit.
1. Check the sensor wiring.
2.Replace the new water temperature
sensor.
Piping temperature sensor
failure
Piping temperature sensor open
circuit or short circuit.
1. Check the sensor wiring.
2.Replace the new piping temperature
sensor.
Ambient temperature
sensor failure
Ambient temperature sensor
open circuit or short circuit.
1. Check the sensor wiring.
2.Replace the new water temperature
sensor.
Too low or too high
ambient temperature
protection
1. Ambient temperature is out of
operating range:11
℃
- 42
℃
.
2. Controller failure.
1. Wait the ambient temperature rising
to 13
℃
or cooling down to 40
℃
to
restart.
2. Replace the new controller.
1. Insufficient or no water flow.
2. The wiring for water flow
switch is in loose situation.
1. Check the water pump or water
piping system.
2. Check the wiring or change a new
water flow switch.