Watlow EZ-ZONE
®
PM PID Controller 64 Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter name
Description
Range Default Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Data
Type
&
Read/
Write
[``P1]
[prof]
Profiling Menu
[``p1]
[ P1] to
[``p4]
[ P4]
Step
Select a step to edit or view.
1 to 10 [profile 1]
11 to 20 [profile 2]
21 to 30 [profile 3]
31 to 40 [profile 4]
Always
[S;typ]
[S.typ]
Step Type
Select a step type.
Note:
When configuring the
profile type there will be a
Time prompt as delivered
from the factory (default).
If rate is desired navigate
to the Setup Page and then
the Global Menu where
Ramping Type can be
changed.
[UStP] Unused Step (50)
[`End] End (27)
[``JL] Jump Loop (116)
[CloC] Wait For Time
(1543)
[W;bo] Wait For Both (210)
[W;Pr] Wait For Process
(209)
[`W;E] Wait For Event (144)
[SoAH] Soak (87)
[``ti] Time (143)
[rate] Rate (81)
Unused Always Instance 1
Map 1 Map 2
2570 4500
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
1
uint
RWE
[t;SP1]
[t.SP1]
Step Type Parameters
Target Set Point (loop 1)
Select the set point for this
step.
-1,999.000to9,999.000°F
or units
-1,128to5,537.000°C
0.0°For
units
-18°C
Step Type is
set to Time,
Rate, Wait for
Process or Wait
for Both.
Instance 1
Map 1 Map 2
2572 4502
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
2
float
RWE
[hoUr]
[hoUr]
Step Type Parameters
Hours
Select the hours (plus
Minutes and Seconds) for a
timed step.
0 to 99
0 Step Type is
set to Time or
Soak.
Instance 1
Map 1 Map 2
2574 4504
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
3
uint
RWE
[Min]
[Min]
Step Type Parameters
Minutes
Select the minutes (plus
Hours and Seconds) for a
timed step.
0 to 59
0 Step Type is
set to Time or
Soak.
Instance 1
Map 1 Map 2
2576 4506
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
4
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User Set