Benchmark 750-6000 with Edge [i]: Install-Startup Manual
SECTION 2 INSTALLATION
OMM-144_B • GF-217 5/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 30 of 62
NOTE:
It is the responsibility of the customer to source and purchase the appropriate gas regulator
as described above. However, AERCO offers for sale an appropriate regulator, which may
be ordered at the time of unit purchase or separately. Contact your AERCO sales
representative for more information.
On all Benchmark models it is strongly recommended that the pressure regulator be installed a
minimum distance of 10 pipe diameters between the pressure regulator and the nearest
downstream fittings (an elbow or the unit itself), and a minimum of 5 pipe diameters between the
pressure regulator and any upstream fitting, such as elbow or shutoff valve, as shown in Figure
2-7a, below (this recommendation applies to, but is not shown, in Figures 2-7b 2-7d).
Figure 2-7a: BMK750-1000 Gas Regulator and Manual Shut-Off Valve
1” MANUAL
SHUTOFF
VALVE
GAS PRESSURE
REGULATOR
DIRT TRAP
GAS INLET

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals