Benchmark 750-6000 with Edge [i]: Install-Startup Manual
SECTION 2 INSTALLATION
OMM-144_B • GF-217 5/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 32 of 62
Figure 2-7d: BMK5000-6000 Manual Gas Shut-Off Valve Location Dual Fuel
2.9.2.1 Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be positioned
as shown in Figure 2-7a 2-7d. The gas supply regulator must be properly vented to outdoors.
Consult the local gas utility for detailed requirements concerning venting of the supply gas
regulator.
2.9.3 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in the gas supply line upstream of the boiler as shown
in Figure 2-7a 2-7d.
NATURAL
GAS SUPPLY
2” MANUAL GAS
SHUT-OFF VALVE
NATURAL GAS
PRESSURE
REGULATOR
PROPANE PRESSURE REGULATOR
DRIP LEG
DRIP LEG
MINIMUM 10 PIPE
DIAMETERS IN LENGTH