SmartPlate Installation, Operation & Maintenance Manual
APPENDIX A – MODBUS CONTROL AND COMMUNICATION
OMM-0069_0H • SP-100 • 1/30/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 101 of 134
A.2 MODBUS COMMUNICATION INFORMATION
NOTE:
The Eurotherm 2400 Controller supports the MODBUS RTU mode of transmission. The
default settings are as follows: 9600 Baud Rate, one start bit, eight data bits, one stop bit, &
no parity bit.
EUROTHERM SERIES 2400 CONTROLLER MODBUS POINTS
140°F, Address to
read value
140°F, Address to
change value
Same value as front
display
13 (set)
74 (status,
0 = safe
1 = alarm)
20°F above setpoint;
Alarm Type 17:
Deviation High
14 (set)
74 (status,
0 = safe
1= alarm)
205 ° F
Alarm Type 2: Full
Scale High
Status:
0: Good
1: Failed
Denotes Feedback
Sensor Failure/Open
Circuit
Sensor input to
controller, same as
display temp.
Sensor input to
controller
Correlates to valve
position
REFERENCE DOCUMENTS:
1. Eurotherm 2000 Series Communications Handbook, # HA026230
2. Eurotherm 2404/2408 Control Setpoint Programmer Installation and Operation
Handbook, # HA025132