Menus
Home Screen
Parameter Range Description
HOME SCREEN
CONDENSATE
-32 to 266°F
(-55.0 to 65.0°C)
The condensate return temperature.
OUTDOOR
-67 to 149°F
(-35.0 to 130°C)
The outdoor air temperature.
TARGET
100 to 220°F
(38.0 to 104.5 °C)
The condensate return must reach the steam established target to the Heat On cycle.
PRESSURE
0.0 to 15.0 psi
(0 to 105 kPa)
The steam system pressure.
TIME REMAINING
(HEAT ON)
00:00:00 to
02:00:00
The time that the boiler is on during the heating cycle.
TIME REMAINING
(HEAT OFF)
00:00:00 to
02:00:00
The time that the boiler is off during the heating cycle.
SYSTEM INPUTS
ROOM TARGET
35 to 100°F
(1.5 to 38.0°C)
The desired room temperature when an indoor sensor is installed.
BOOST Off or On
Dot is green when Boost is active.
EARLY START Off or On
Dot is green when Early Start is active.
SMART SETBACK Off or On
Dot is green when Smart Setback is active.
DOMESTIC HOT
WATER
Off or On
Dot is green when DHW call is active.
OUTDOOR
-67 to 149°F
(-35.0 to 130°C)
The outdoor air temperature.
CONDENSATE
-32 to 266°F
(-55.0 to 65.0°C)
The condensate return temperature.
INDOOR
35 to 100°F
(1.5 to 38.0°C)
The indoor sensor temperature.
PRESSURE
1.0 to 15.0 psi
(0 to 105 kPa)
The steam system pressure.
SYSTEM STATUS
COMBUSTION AIR Off or On
Dot is green when combustion air damper is open.
WARM WEATHER
SHUT DOWN
Off or On
Dot is green when warm weather shut down is in effect.
OVERRIDE
Auto, Hand, Max
Heat, Off
The manual override status.