22
Settings (5 of 5)
Parameter Range Description
ALERTS
BOILER PLANT
NO HEAT ALERT
ENABLE
Off or On
Default: Off
Select if an alert is triggered if the condensate return temperature does not increase.
Requires a condensate sensor to be installed.
BOILER PLANT NO
HEAT ALERT
5.0 to 80.0 minutes
Default: 60.0 minutes
Set the amount of time of no temperature change while boilers are firing after which
the control triggers a boiler plant no heat alert notification. Requires a condensate
sensor to be installed.
HIGH PRESSURE
ALERT
0.0 to 15.0 psi
(0 to 105 kPa)
Default: 15.0 psi
(105 kPa)
Set the threshold above which the control triggers a high pressure alert notification.
FLUE
TEMPERATURE
ALERT
100 to 392°F
(38.0 to 200.0°C)
Default: 392°F (200.0°C)
Set the threshold above which the control triggers a flue temperature alert notification.
INDOOR
TEMPERATURE
COLD ALERT
ENABLE
Off or On
Default: Off
Select if an alert is triggered if the indoor temperature falls below the threshold.
Requires an indoor sensor to be installed.
INDOOR
TEMPERATURE
COLD ALERT
32 to 100°F
(0.0 to 38.0 °C)
Default: 38°F (3.5°C)
Set the threshold below which the control triggers an indoor temperature cold alert
notification. Requires an indoor sensor to be installed.
INDOOR
TEMPERATURE HOT
ALERT ENABLE
Off or On
Default: Off
Select if an alert is triggered if the indoor temperature exceeds the threshold. Requires
an indoor sensor to be installed.
INDOOR
TEMPERATURE HOT
ALERT
32 to 100°F
(0.0 to 38.0 °C)
Default: 78°F (25.5°C)
Set the threshold below which the control triggers an indoor temperature hot alert
notification. Requires an indoor sensor to be installed.
BOILER 1 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification.
BOILER 1 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification.
BOILER 2 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification.
BOILER 2 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification.
SECURITY
STEP 1 N/A
Set a personal passcode. This is required when a passcode has already been set.
STEP 2 N/A
Confirm the personal passcode. This is required when a passcode has already
been set.
REQUIRE
PASSCODE
Off or On
Default: Off
Select if a passcode is required to enter the Home screen.
PASSCODE N/A
Select to change the personal passcode. Redirects user to Steps 1 and 2.