Notifications Menu
The control keeps track of the last 30 errors and alert
notifications.
Refer to the Troubleshooting section for corrective action.
Overrides Menu
Parameter Range Description
OPERATION
Automatic, Hand,
Purge, Max Heat, Off
Set the manual override.
Automatic reverts to normal operation.
Hand allows each output to be turned on or set manually.
Max Heat operates the heating system at the boiler maximum setting.
Off places the control into a standby state and the boilers and pumps are not operated.
COMBUSTION AIR
DAMPER
Off or On
Default: Off
Select to turn on the combustion air damper. Available in Hand override.
BOILER 1 ENABLE
Off or On
Default: Off
Set on to fire the boiler. Available in Hand override when Boiler 1 Enable is on.
Available in Hand override.
BOILER 2 ENABLE
Off or On
Default: Off
Set on to fire the boiler. Available in Hand override when Boiler 2 Enable is on.
Available in Hand override.
BOILER MAX HEAT
PERCENTAGE
5% to 100%
Default: 100%
Select the boiler run time percentage of the heating cycle. Available when set to
Max Heat Override.