Wiring Schematic
This section provides a wiring schematic for the control.
Before wiring, ensure all power is turned off and take all
necessary precautions.
Sensor wiring may be extended to a total length of
500 feet (152 m) using 18 AWG solid conductor wire.
Strip all wiring to a length of
3
8 in. or 10 mm for all terminals.
A circuit breaker or power disconnect that provides power
to the control should be located nearby and clearly labeled.
Refer to the current and voltage ratings at the back of this
brochure before connecting devices to this control.
Only qualified personnel should install or service the control.
FCC ID: 2AHQR-11500A
Contains FCC ID:
2AC7Z-ESP32WROOM32E
QOQMGM12P0
Contains IC ID:
21098-ESPWROOM32E
5123A-MGM12P0
CAN ICES-3 (A)/NMB-3(A)
Class 2 Circuits
Input Power:
115 V (ac) ±10%, 60 Hz, 4 W
Relays:
230 V (ac), 5 A, 1/3 hp
Calls:
24 V (ac) or Short
Operating Temperature:
32°F to 122°F (0°C to 50°C)
Use Copper Conductors Only
Wi-Fi: 802.11b/g/n, 2.4GHz
12
10/100
Ethernet
14
13
Boiler 1
Enable
1615
Boiler 2
Enable
1817
Comb
Air Relay
2019
Power
N
DANGER
DANGER
To Reduce the Risk of Electric
Shock - Do not connect to a
circuit operating at more than
150 volts to ground.
Pour réduire les risques
d'électrocution choc - ne pas
raccorder à un circuit
fonctionnant à plus de 150 V à
la terre.
L
54
Outdoor
76
Cond
Sensor
98
Aux
Sensor
1110
DHW
231
Ref In Gnd
Pressure Sens
Call
+
Sensor
H2065A
Smart Steam Control 289
For product literature:
Pour la documentation
du produit:
tekmarControls.com
tektra 1150-02
Designed and assembled
in Canada
N
G
L
TT TT
L
NG
As with any electrical product, care should be taken to
guard against the potential risk of fire, electric shock, and
injury to persons