SPECIFICATIONS
MODELS
HSG2OO, HSG4OO
NATURAL
OR
PROPANE
GAS
NOTE: Dimensions in
(
)
are
informational
only.
English values take
priority.
HSG2OO
Maximum lnput
Capacity
-
200
MBtu/HR
(211000
kJ)
Minimum Input
Capacity
-
60
MBtu/HR
(63300
kJ)
HSG4OO
Maximum Input Capacity
-
400 MBtu/HR
(422000
kJ)
Minimum Input
Capacity
-
200 MBtuiHR
(211000
kJ)
SUPPLY LINE PRESSURE REQUIRED: Natural or Propane 5.5 W.C.
(1370
Pa) Minimum, 14.0 WC.
(3487
Pa)
Maximum
AIR TUBE DIAMETER: 4 inches
(101.6
mm)
AIR TUBE LENGTHS: HSG200 6 inches
(152.4
mm)
(See
Fig.
12C
tor HSG400
6.25
inches
(158.75
mm)
Overall Dimensions)
HSG200|4O0
9.00
inches
(228.6
mm)
HSG200/400 12.00
inches
(304.8
mm)
MOUNTING: Adjustable flange standard
(deduct
1 1/8 inch
(28.575
mm) from
above air tube
lengths when using
flange). Optional
pedestal
mounting.
STANDARDVOLTAGE: 120VAC I60HZl 1 Phase
120
VAC
| 50 HZ 1 Phase
(Special
motor installed with max
capacity
reduced 20%)
220VACl50HZl 1 Phase
FLAME SAFETY: 24 VAC Electronic
IGNITION:
7300 VAC Direct
Spark
GAS VALVE=314x
3/4
(19.05
mm x 19.05 mm) NPT
3
Function Redundant 24VAC
.200
MBtu/HR
(211000
kJ)
(200,000
BTU
[58.62
kW] / HR) or 400 MBtu/HR
(42200
kJ)
(400,000
BTU
[117.24
kW]
/ HR)
at sea
level. Derate input for altitude
over
2000 tt.
(609.6
m)
by
4"/. each 1000 ft.
(304.8
m)
above sea
level.
(one
gallon
(3.79
L) fueloil
=
140 MBtu/HR
(14770
kJ)).
CONTENTS
PAGE
sEcTtoN I tNSTALLATION ............ ..1
C. HEATING APPLIANCE INSPECTION. .........-...-.2
D.
CHIMNEY
FLUE PIPE AND DRAFT
CONTROL ..............2.3
E.
COMBUSTTON CHAMBER .............4
G. ELECTRICAL
H. MAIN BURNER
ORIFICE SIZING
AND INSTALLATION
........................5
r.
CoMBUSTTON GAS VA1VE........ ........................6
SECTION III OPERATION AND
TROUBLESHOOTING..
...........9.14
SECTION IV SERVICE
EXPLODED
VIEW
TECHNICAL
INFORMATION.,........
SPECIFICATIONS MODELS
HSG200, HSG400
NATURAL
OR
PROPANE GAS
NOTE: Dimensions
in
( ) are informational only. English values take priority.
HSG200
Maximum Input Capacity - 200 MBtu/HR (211000 kJ)
Minimum Input Capacity - 60 MBtu/HR (63300 kJ)
HSG400
Maximum Input Capacity - 400 MBtu/HR (422000 kJ)
Minimum Input Capacity - 200 MBtu/HR (211000 kJ)
SUPPLY LINE PRESSURE REQUIRED: Natural or Propane 5.5 W.C. (1370 Pa) Minimum, 14.0 W.C. (3487 Pa)
Maximum
AIR TUBE DIAMETER: 4 inches (101.6 mm)
AIR TUBE LENGTHS: HSG200
(See Fig. 12C for HSG400
Overall Dimensions) HSG200/400
HSG200/400
6 inches
6.25 inches
9.00 inches
12.00 inches
(152.4 mm)
(158.75 mm)
(228.6 mm)
(304.8 mm)
MOUNTING: Adjustable flange standard (deduct 1 1/8 inch (28.575 mm) from above air tube lengths when using
flange). Optional pedestal mounting.
STANDARD VOLTAGE: 120 VAC 160
HZ/1
Phase
120 VAC
150
HZ/1
Phase (Special motor installed with max capacity reduced 20%)
220 VAC
150
HZ/1
Phase
FLAME SAFETY: 24 VAC Electronic
IGNITION: 7300 VAC Direct Spark
GAS VALVE: 3/4 x 3/4 (19.05 mm x 19.05 mm) NPT 3 Function Redundant 24 VAC
*200 MBtu/HR (211000 kJ) (200,000 BTU [58.62 kW]
1HR) or 400 MBtu/HR (42200 kJ) (400,000 BTU [117.24 kW]
1HR) at sea level. Derate input for altitude over 2000
ft.
(609.6
m)
by 4% each 1000 ft. (304.8
m)
above sea level.
(one gallon (3.79
L)
fuel oil =140 MBtu/HR (14770 kJ)).
CONTENTS
PAGE
SECTION I INSTALLATION
1
A.
GENERAL 2
B.
VENTILATION 2
C.
HEATING APPLIANCE INSPECTION 2
D.
CHIMNEY, FLUE PIPE AND DRAFT CONTROL 2-3
E.
COMBUSTION CHAMBER 4
F.
GAS PIPING 4
G.
ELECTRiCAL 5
H.
MAIN BURNER ORIFICE SIZING AND INSTALLATION 5
I.
COMBUSTION GAS VALVE 6
SECTION
II
INITIAL START UP
7-8
SECTION III OPERATION AND TROUBLESHOOTING 9-14
SECTION IV SERVICE 15-16
PARTS LISTS
17
EXPLODED VIEW
18
TECHNICAL INFORMATION 19
WARRANTy
20
CONSUMER INSTRUCTIONS
21