WECON VM AC Drive User Manual V2.0
WECON technology Co., Ltd
- 25 -
Code
Name
Range
Default
Feature
RAM
address
FD.11
INNER PLC(AND
MULTI-STAGE
SPEED)11
0.0 to 100.0% * F0.10
0
0D0B
FD.12
INNER PLC(AND
MULTI-STAGE
SPEED)12
0.0 to 100.0% * F0.10
0
0D0C
FD.13
INNER PLC(AND
MULTI-STAGE
SPEED)13
0.0 to 100.0% * F0.10
0
0D0D
FD.14
INNER PLC(AND
MULTI-STAGE
SPEED)14
0.0 to 100.0% * F0.10
0
0D0E
FD.15
INNER PLC(AND
MULTI-STAGE
SPEED)15
0.0 to 100.0% * F0.10
0
0D0F
FD.16
Inner PLC Running
Mode
0: Stop after a single cycle
1: Continuous loop
2: Hold the final value after
a single cycle
0
0D10
FD.17
Inner PLC Power-off
Memory Option
0: Invalid, 1: Valid
0
0D11
FD.18
Inner PLC Stage 0
Running Period
0.0 to 6500.0(s/m/h)
10.0
0D12
FD.19
Inner PLC Stage 0
Direction &
Acceleration &
Deceleration Time
LED Ones Place: Direction
of the Stage
0: FWD, 1: REV
LED Tens Place:
Acceleration &
Deceleration Time
0: Acceleration &
Deceleration Time 1
1: Acceleration &
Deceleration Time 2
2: Acceleration &
Deceleration Time 3
3: Acceleration &
Deceleration Time 4
LED Hundreds Place:
Reserved
LED Thousands Place:
Reserved
0
0D13
FD.20
Inner PLC Stage 1
Running Period
0.0 to 6500.0(s/m/h)
10.0
0D14
FD.21
Inner PLC Stage 1
Direction &
Acceleration &
Deceleration Time
Same as FD.19
0
0D15