Installation Guide
8 | CFW-11
ENGLISH
Do not install heat sensitive components right above the inverter.
NOTE!
The detailed description of all models (IP2X/IP55) of
the CFW-11 frequency inverter is found in the user's
manual, available for download on www.weg.net.
CABINET MOUNTING
Surface assembly:
Provide adequate exhaustion so that the internal cabinet temperature
remains within the allowed range for the inverter operations
conditions.
The power dissipated by the inverter at its rated condition is specified
in table A.1, A.2, A.3 and A.4 “Dissipated power in Watts – Surface
Mounting”.
The cabinet minimum air cooling flow requirements are as shown
in table 1.
The position and diameter of the mounting holes are according to
figure 1.
A1
B1
E1
D1
C1
Frame Sizes A...E
Air flow
a2
b2
øc2
Air flow
Max. 3 mm
(0.12 in)
b3
e3
øc3
a3
d3
Frame Sizes F...H
Air flow
a2 a2
b2
øc2
Air flow
Max. 3 mm
(0.12 in)
a3
b3
e3
øc3
d3
Surface mounting Flange mounting
Model
A1 B1 C1 D1 E1 a2 b2 c2 a3 b3 c3 d3 e3 f3
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
M
mm
(in)
mm
(in)
M
mm
(in)
mm
(in)
M
Frame
size A
145
(5.71)
247
(9.73)
227
(8.94)
70
(2.75)
270
(10.63)
115
(4.53)
250
(9.85)
M5
130
(5.12)
240
(9.45)
M5
135
(5.32)
225
(8.86)
M5
Frame
size B
190
(7.4 8)
293
(11.5 3)
227
(8.94)
71
(2.78)
316
(12.43)
150
(5.91)
300
(11.82)
M5
175
(6.89)
285
(11. 23)
M5
179
(7.0 5)
271
(10.66)
M5
Frame
size C
220
(8.67)
378
(14.88)
293
(11.5 3)
136
(5.36)
405
(15.95)
150
(5.91)
375
(14.77)
M6
195
(7.6 8)
365
(14.38)
M6
205
(8.08)
345
(13.59)
M8
Frame
size D
300
(11.81)
504
(19.84)
305
(12.00)
135
(5.32)
550
(21.65)
200
(7.8 8)
525
(20.67)
M8
275
(10.83)
517
(20.36)
M8
285
(11. 23)
485
(19.10)
M6
Frame
size E
335
(13.19)
620
(24.41)
358
(14.09)
168
(6.61)
675
(25.57)
200
(7.8 8)
650
(25.59)
M8
275
(10.83)
635
(25.00)
M8
315
(12.40)
615
(24.21)
M8
Frame
size F
430
(16.93)
1156
(45.51)
360
(14.17 )
169
(6.65)
1234
(48.58)
150
(5.91)
1200
(47.24)
M10
350
(13.78)
1185
(46.65)
M10
391
(15.39)
1146
(45.12)
M8
Frame
size G
535
(21.06)
1190
(46.85)
426
(16.77)
202
(7.9 5)
1264
(49.76)
200
(7.87)
1225
(48.23)
M10
400
(15.75)
1220
(48.03)
M10
495
(19.49)
1182
(46.53)
M8
Frame
size H
686 13 1 9.7 420.8 171.7 1414 175 1350
M10
595 1345
M10
647 1307 -
Tolerance for d3 and e3: +1.0 mm (+0.039 in)
General tolerance: ±1.0 mm (±0.039 in)
Figure 1: Mechanical installation details
A
B
C
D D
Ventilation Clearances
Model
A B C D
mm (in) mm (in) mm (in) mm (in)
Frame size A 25 (0.98) 25 (0.98)
10 (0.39) 30 (1.18)
Frame size B 40 (1.57) 45 (1.77)
Frame size C
110 (4.33) 130 (5.12)
Frame size D
Frame size E
0142 T2 100 (3.94) 130 (5.12)
20 (0.78)
40 (1.57)
0180 T2
150 (5.91) 250 (9.84) 80 (3.15)
0211 T2
0105 T4 100 (3.94) 130 (5.12) 40 (1.57)
0142 T4
150 (5.91) 250 (9.84) 80 (3.15)
0180 T4
0211 T4
Frame size F
Frame size G
Frame size H
Tolerance: ±1.0 mm (±0.039 in)
Figure 2: Minimum clearance for inverter ventilation
Table 1: Minimun required cabinet cooling air flow
Frame size Model CFM I/s m³/min
A All 18 8 0.5
B All 42 20 1.2
C All 96 45 2.7
D All 132 62 3.7
E
CFW110142T2 180 95 5.1
CF W11018 0T2 an d 0211T2 265 125 7.5
CFW110105T4 138 65 3.9
CFW110142T4 180 95 5.1
CF W11018 0T4 and 0211T4 265 125 7.5
CFW110053T6, 0063 T6 and 0080T6 180 95 5.1
CFW110107T6, 0125T6 and 0150T6 265 125 7.5
F
CFW110242T4 250 118 7.1
CF W110312T4 320 151 9.1
CF W110370T4 380 180 10.1
CF W110477 T4 460 217 13.0
CFW110170T6, 0216T6 and 0289T6 460 217 13.0
G
CFW110515T4, 0601T4 and 0720T4 680 321 19.3
CF W110760T4 1020 481 28.9
CFW110315T6, 0365T6 and 0435T6 680 321 19.3
CF W110472T6 1020 481 28.9
H All 1100 520 31.2
Flange mounting:
The losses specified in table A.1, A.2, A.3 and A.4, “Dissipated power
in Watts - Flange mounting” will be dissipated inside the cabinet. The
remaining losses will be dissipated through the back side.