8 | CFW100
State HMI Description
PARAM
PASTE
ERROR
Indicates an error occurred in the
download
(CFW100-MMF CFW100) of
the inverter parameter table.
SOFTPLC
PASTE
ERROR
Indicates an error occurred in the
download
(CFW100-MMF CFW100) of
the inverter SoftPLC application.
The possible causes of the “ErrC” and “ErrP” errors are:
Low battery during the transfer.
Disconnection of the cable during the transfer.
Incompatibility of firmware versions during download
of the inverter parameter table (paste function)
indicating “ErrP” on the display.
6 INDICATIONS ON THE INVERTER
DISPLAY (CFW100)
State HMI Description
NORMAL Normal operating condition.
FAULT
Indication of communication fault
between the CFW100-MMF and
the CFW100 (F082). This fault
can be reset by means of the
switch indicated in Figure A.3 on
page 21.
ALARM
Alarm indication in the attempt
to copy protected SoftPLC user
program from the CFW100.
The possible causes of F082 fault are:
Data transfer using the paste function
(CFW100-MMF CFW100) with invalid data and/or
incompatible software version.
Attempt of connection and data transfer with the
(CFW100) inverter energized.
The possible causes of alarm A712 are:
Attempt to copy SoftPLC program protected against
copies (“never permit to copy").
Attempt to copy the SoftPLC program from a
protected copy ("never permit to copy from a copy").