Quick Installation Guide
CFW300 Micro Drive
1 SAFETY INSTRUCTIONS
This quick installation guide contains the basic information necessary to commission the CFW300. It has
been written to be used by qualified personnel with suitable training or technical qualification for operating
this type of equipment. The personnel shall follow all the safety instructions described in this manual
defined by the local regulations. Failure to comply with the safety instructions may result in death, serious
injury, and/or equipment damage.
2 SAFETY WARNINGS IN THE MANUAL
NOTE!
It is not the intention of this guide to present all the possibilities for the application of the
CFW300, as well as WEG cannot take any liability for the use of the CFW300 which is not
based on this guide.
For further information about installation, full parameter list and recommendations, visit the
website www.weg.net.
DANGER!
The procedures recommended in this warning have the purpose of protecting the user
against death, serious injuries and considerable material damage.
ATTENTION!
The procedures recommended in this warning have the purpose of avoiding material damage.
NOTE!
The information mentioned in this warning is impor tant for the proper understanding and
good operation of the product.
High voltages are present.
Components sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to the protective ground (PE).
Connection of the shield to the ground.
3 PRELIMINARY RECOMMENDATIONS
DANGER!
Always disconnect the main power supply before touching any electrical component
associated to the inverter. Several components can remain charged with high voltages or
remain in movement (fans) even af ter the AC power is disconnected or switched off. Wait at
least ten minutes after turning off the input power for the complete discharge of the power
capacitors. Always connect the grounding point of the inverter to the protection ear th (PE).
The XC10 connector does is not USB compatible, therefore, it cannot be connected to
USB ports.
This connectors ser ve only as interface between the CFW300 frequency inverter and its
accessories.
NOTE!
Frequency Inverter may inter fere with other electronic equipment. Follow the precautions
recommended in manual available in www.weg.net.
Do not per form any withst and voltage test!
If necessary, contact the manufacturer.
ATTENTION!
Electronic boards have components sensitive to electrostatic discharges.
Do not touch directly on components or connectors. If necessary, first touch the grounding
point of the inverter, which must be connected to the protection ear th (PE) or use a proper
grounding strap.
ATTENTION!
When the inverter is stored for a long period, it becomes necessary to per form the capacitor
reforming. Refer to the procedure recommended in www.weg.net.
4 ABOUT THE CFW300
The CF W300 frequency inverter is a high-performance product which allows speed and torque control of
three-phase induction motors. This product provides the user with the options of vector (V V W) or scalar
(V/f) control, both programmable according to the application.
5 TERMINOLOGY
Tab l e 1: Terminology of the CFW300 inve rters
Product
and Series
Model Identification
Brake
Degr ee of
Protection
Hardware
Vers ion
Software
Vers ion
Frame
Size
Rated
Current
Phase
Number
Rated
Volt age
Ex.: CFW300 A 01P6 S 2 NB 20 --- ---
Available
options
CFW300
Refer to Table 2 Blank = standard
NB = without braking reostática Sx = special software
DB = with braking reostática Blank = standard
20 = IP20 Hx = special hardware
Tab l e 2 : Available options for each field of the nomenclature according to the rated curre nt and voltage of the inverter
Frame Size
Output Rated
Current
N° of Phases Rated Voltage Brake
A
01P6 = 1.6 A
S = single-phase power supply
1 = 110...127 Vac
NB
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
01P6 = 1.6 A
2 = 200...240 Vac
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
T = three-phase power supply
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
01P6 = 1.6 A
D = DC power s upply 3 = 280...340 Vdc
02P6 = 2.6 A
04P2 = 4.2 A
06P0 = 6.0 A
07P3 = 7.3 A
B
10P0 = 10.0 A B = single-phase or three-phase power supply or DC
2 = 200...240 Vac
or 28 0...340 Vdc
DB
15P2 = 15 .2A T = three-phas e power supply or DC
6 RECEIVING AND STORAGE
The CF W300 is supplied packed in a cardboard box. There is an identification label affixed to the outside
of the package, identical to the one affixed to the side of the inverter.
Verify whether:
The CFW300 identification label corresponds to the purchased model.
Any damage occurred during transportation.
Report any damage immediately to the carrier.
If the CF W300 is not installed soon, store it in a clean and dry location (temperature between -25 ºC and
60 ºC (-13 ºF and 140 ºF)), with a cover to prevent dust accumulation inside it.
7 IDENTIFICATION LABEL
Production order
Rated input data
(voltage, current and
frequency)
Serial number
Manufacturing date (14 corresponds
to the week and I to the year)
Rated output data
(voltage, current and frequency)
WEG stock item
Model (Inverter
intelligent code)
Figure 1: Description of the CFW300 identification label
8 DIMENSIONS
View of th e mounting base Front view Side view
PLA
B
H
Frame
Size
A B H L P Weight
Mounting
Bolt
Recommended
Torque
mm
(in)
mm
(in)
mm
(in)
mm
(in)
mm
(in)
kg
(lb)
N.m (Ibf.in)
A 35 .0 (1. 37 ) 50.1 ( 1. 9 7 ) 157.9 (6.22) 70.0 (2.76) 148 .4 (5,84 ) 0.900 (1.98) M4 2 (1 7.7 )
B 35.0 (1.37) 50 .1 (1. 97) 198.9 (8.08) 70.0 (2.76) 158.4 (6.24) 1.3 40 (2.98 ) M4 2 (1 7.7 )
Dimension tolerance: ±1,0 mm (±0,039 in)
Figure 2: Inverter dimensions for mechanical installation
9 INSTALLATION AND CONNECTION
Environmental Conditions
Avoid:
Direct exposure to sunlight, rain, high humidity or sea-air.
Inflammable or corrosive gases or liquids.
Excessive vibration.
Dust, metallic particles or oil mist.
Environment conditions permitted for the operation of the inverter:
Temperature surrounding the inverter: 0 ºC to 50 ºC ( 32 ºF to 122 ºF) – IP20.
For temperatures surrounding the inverter higher than the specifications above, it is necessary to apply
of 2 % of current derating for each degree Celsius, limited to an increase of 10 ºC (50 ºF).
Air relative humidity: 5 % to 95 % non-condensing.
Maximum altitude: up to 1000 m (3.300 f t) - rated conditions.
From 1000 m to 4000 m (3.300 ft to 13.200 ft) – 1 % of current derating for each 100 m above 1000 m
of altitude.
Pollution degree: 2 (according to EN50178 and UL508C), with non-conductive pollution. Condensation
must not originate conduction through the accumulated residues.
10 ELECTRICAL INSTALLATION
DANGER!
The following information is merely a guide for proper installation. Comply with applicable
local regulations for electrical installations.
Make sure the AC power supply is disconnected before starting the installation.
The CFW300 must not be used as an emergency stop device. Provide other devices
for that purpose.
2
2
1
1
5
4
3
1 - power termina ls
2 - grounding points
3 - connector of the
communication accessory
4 - control terminals
5 - conne ctor of the I/O
expansion accessory
Frame
Size
Recommended Torque
Grounding
Points
Power
Terminal
N.m Lbf.in N.m Lbf.in
A and B 0.8 7. 2 0.8 7. 2
Figure 3: Power terminals, grounding points and re commended tightening torque
10 .1 POWER CONNECTIONS
Description of the power terminals:
L/L1, N/L2, L3 (R,S,T): power supply connection.
U, V and W: connection for the motor.
-UD: negative pole of the DC power supply.
+UD: positive pole of the DC power supply.
+BR, BR: connection of the braking resistor (available for frame size B models).
PE: grounding connection.
(a) Frame size A DC power supply (b) Frame size A single-phase and three-phase power supply
Shielding
Negati ve pole of the DC power s upply (-UD)
Shielding
Shielding
Shielding
Fuses
Positiv e pole of the D C power supply (+UD)
Disconnecting
switch
Fuses
Fuses
Fuses
PE
Disconnecting
switch
PE
PE -UD +UD
PE V
PEW UV
U W
Power
supply
PE L1 L2 L3
L1/ L
L2/N
L3*
Negati ve pole of the DC powe r supply (-UD)
Positiv e pole of the DC power s upply (+UD)
Power
supply
Disconnecting
switch
Disconnecting
switch
PE
-UD
-UD
+BR
+BR
+UD
+UD
BR
BR
PE
L1/ L
L2/N
L3
Power
supply
PE V
PEW UV
U W
PE
PE
L1
L1
L2
L2
L3
L3
PE
PE
V
V
PE
PE
W
W
U
U
V
V
U
U
W
W
Power
supply
(*) The power te rminal L3 is not ava ilable i n models of frame s ize
A single-phase
Only ava ilable f or the 10-A mod el (see table 2).
Only ava ilable f or the spe cific models of fr ame size A (s ee table 2).
(c) Frame size B DC power supply
(d) Frame size B single-phase a nd thre e-phase power supp ly
Figure 4: (a) to (d) Powe r and grounding connections
10.2 INSTALLATIONS ACCORDING TO EUROPEAN DIRECTIVE OF ELECTROMAGNETIC
COMPATIBILITY
The CF W300 inverter series, when properly installed, meet the requirements of the directive of the
electromagnetic compatibility.
These inverters were developed for professional applications only. Therefore, the emission limits of
harmonic currents by the standards EN 61000-3-2 and EN 61000-3-2/A 14.
10 . 2 .1 Conformal Installation
1. Shielded output cables (motor cables) with shield connected at both ends, motor and inverter, by meanse
of a low impedance to high frequency connection. Maximum motor cable length and conduced and
radiated emission levels according to Table 6.
2. Shielded control cables, keeping the separation distance from other cables according to Table 3.2 the
user's manual.
3. Grounding of the inverter according to instruction of the 3.2.4 Grounding Connections the user's manual.
4. Grounded power supply.
5. Use short wiring to ground the external filter or inver ter.
6. Ground the mounting plate using a flexible braid as short as possible. Flat conductors have lower
impedance at high frequencies.
7. Use sleeves for cable conduits whenever possible.
The CF W300 is suitable for application in a circuit able to supply not more than 30.000 symetric Arms
maximum of 127 / 240 V, when protected by fuses classified as indicated below:
Tab l e 3 : L ist of models of CFW300 series, main electrical specifications
Inverter
Number of Input Phases
Power Suppl y Rated Volt age
Frame Size
Output Rated Current
Overload Currents
Maximum Motor
Circuit Breaker
Recommended Fuse
Power Wire Size
Grounding Wire Size
Dynamic Braking
I²t [A² s]
Current
Recommended Fuse WEG
Maximum Current
Recommended
Resistor
Braking rms Current
Power Wire Si ze for
DC+ and BR Terminals
[Arms]
1 min
[Arms]
[HP/ kW ]
[A]
WEG
[A]
mm²
(AWG)
mm²
(AWG)
(Imax)
[A]
[Ω]
[A]
mm²
(AWG)
CF W3 00A0 1P6 S1NB 20 1 11 0. ..1 27 Vac A 1.6 2.4 0.25/0.18 10.0 MPW40-3-U010 16 6 20 FNH00-20K-A 1.5 (16) 2.5 (14)
Dynamic braking
not available
CFW300A02P6S1NB20 1 110 .. .12 7 Va c A 2.6 3.9 0.5/0.37 16 .0 MPW40-3-U016 166 20 FNH00-20K-A 2.5 (14) 2.5 (14)
CFW300A04P2S1NB20 1 110 .. .12 7 Va c A 4.2 6.3 1/0.75 20.0 MPW40-3-U020 660 35 FNH00-35K-A 2.5 (14) 4.0 (12)
CFW300A06P0S1NB20 1 110 ...12 7 V ac A 6.0 9.0 1. 5/ 1.3 2 32.0 MPW40-3-U032 660 40 FNH00-40K-A 4.0 (12) 4.0 (12)
CFW300A01P6S2NB20 1 200... 240 Va c A 1. 6 2.4 0.25/0.18 6.3 MPW40-3-D063 166 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6S2NB20 1 200 ...240 Vac A 2. 6 3.9 0.5/0.37 10 .0 MPW40-3-U010 16 6 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2S2NB20 1 200...240 Va c A 4.2 6.3 1/0.75 16 .0 MPW40-3-U016 16 6 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A06P0S2NB20 1 200...240 Va c A 6.0 9.0 1.5 /1. 32 16.0 MPW40-3-U016 660 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3S2NB20 1 2 00... 240 Va c A 7. 3 11. 0 2/ 1.5 20.0 MPW40-3-U020 660 25 FNH00-25K-A 2.5 (14) 4.0 (12)
CFW300A01P6T2NB20 3 200...240 Va c A 1.6 2.4 0.25/0.18 2.5 MPW40-3-D025 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6T2NB20 3 200 ...240 Vac A 2. 6 3.9 0.5/0.37 6.3 MPW40-3-D063 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2T2NB20 3 200 ...240 Vac A 4. 2 6.3 1/0.75 10.0 MPW40-3-U010 500 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW30 0A06P0T2N B20 3 200 ...240 Vac A 6.0 9.0 1.5 /1. 32 10.0 MPW40-3-U010 50 0 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3T2NB20 3 200...240 Vac A 7. 3 11. 0 2 /1.5 16.0 MPW40-3-U016 500 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A01P6D3NB20 1 280 ...34 0 Vdc A 1.6 2.4 0.25/0.18 2.5 MPW40-3-D025 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A02P6D3NB20 1 28 0...3 40 Vd c A 2.6 3.9 0.5/0.37 6.3 MPW40-3-D063 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A04P2D3NB20 1 28 0...340 Vd c A 4.2 6.3 1/0.75 10.0 MPW40-3-U010 - 20 FNH00-20K-A 1.5 (16) 2.5 (14)
CFW300A06P0D3N B20 1 28 0...3 40 Vd c A 6.0 9.0 1. 5/ 1.3 2 10 .0 MPW40-3-U010 - 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300A07P3D3NB20 1 280 ...34 0 Vdc A 7. 3 11. 0 2/1.5 16. 0 MPW40-3-U016 - 20 FNH00-20K-A 2.5 (14) 4.0 (12)
CFW300B10P0B2DB20 1/3
200...240 Vac ou
280...340 Vdc
B 10 .0 15.0 3 /2.2 25.0 MPW40-3-U025 300 35 FNH00-35K-A 2.5 (14) 4.0 (12) 11 39 10
2.5
(14)
CFW300B15P2T2DB20 3
200...240 Vca ou
280...340 Vcc
B 15 .2 22.8 5/3.7 25.0 MPW40-3-U025 685 35 FNH00-35K-A 4.0 (12) 4.0 (12) 11 39 10
2.5
(14)
DANGER!
The inverter must be connected to a protective ground (PE).
Use a minimum wire gauge for ground connection equal to the indicated in Table 3.
Connect the inverter grounding connections to a ground bus bar, to a single ground point
or to a common grounding point (impedance ≤ 10 Ω).
The neuter conductor of the line that feeds the inverter must be solidly grounded; however
this conductor must not be used to ground the inverter.
Do not share the grounding wiring with other equipment that operate with high currents
(e.g.: high voltage motors, welding machines, etc.).
NOTE!
The wire gauges listed in Table 3 are guiding values. Installation conditions and the maximum
permitted voltage drop must be considered for the proper wiring sizing.
10.3 CONTROL CONNECTIONS
DI1DI1
DI2DI2
DI3DI3
DI4DI4
+10 V+10 V
GNDGND
GNDGND
1
1
10
10
11
11
12
12
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
(+) AI1 (-)
(+) AI1 (-)
(0 to 20) mA
(0 to 20) mA
(4 to 20) mA
(4 to 20) mA
(0 to 10) V
(0 to 10) V
Counter
clockwise
Counter
clockwise
Clockwise
Clockwise
AI1
AI1
24 V
External supply
DO1-RL-NCDO1-RL-NC
DO1-RL-NODO1-RL-NO
DO1-RL- CDO1-RL- C
(a) NPN Configuration
(b) PNP Configuration
Connector Description
(*)
1 DI1 Digital input 1
2 DI2 Digital input 2
3 DI3 Digital input 3
4 DI4 Digital input 4
5 GND Refere nce 0 V
6 A I1 Analog input 1 (Cu rrent)
7 GND Refere nce 0 V
8 A I1 Analog input 1 (Tension)
9 +10 V Refe rence +10 Vdc for pote ntiometer
10 DO1-RL-NC Digital output 1 (NC contact of relay 1)
11 DO1-RL-C Digital output 1 (Com mon point of relay 1)
12 DO1-RL-NO Digita l output 1 (NO co ntact of relay 1)
(*) For further information, refer to the detailed specification in table 7.
- The CF W300 inverters are supplied with the digital inputs configured
as active low (NPN). In order to change the configuration, c heck the
use of parameter P271 in the programm ing manual of the CFW300.
- Analog inpu t AI1 is set for input 0 to 10 V; in order to change it, c heck
parameter P233 of the programming manual of the CFW300.
Figure 5: (a) and (b) Signals of C300 control card connector
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Ma ximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the connector of the control board with shielded cable and separated from the other wiring
(power, command in 110 V / 220 Vac, etc.).
10 .3.1 Emission and Immunity Levels
Tab l e 4 : Emission and immunity levels
EMC Phenomenon Basic Standard Level
Emission:
Mains terminal disturbance voltage
Freque ncy range: 150 kHz to 30 MHz)
IEC/EN 61800-3
It depe nds on the inver ter model on the length of the
cabo motor cable. Refer to Table 6
Electromagnetic radiation disturbance
Freque ncy Range: 30 MHz to 1000 MHz)
Immunity:
Electrostatic disc harge (ESD) IEC 61000-4-2 4 kV for contact discharge and 8 kV for air disc harge
Fast transient-Burst IEC 61000-4-4
2 kV / 5 kHz (couplin g capacitor) input cables
1 kV / 5 kHz control cables and rem ote HMI cables
2 kV / 5 kHz (couplin g capacitor) motor cables
Conducted Radio-Frequency
Common Mode
IEC 61000-4-6
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz)
Motor, control and remote HMI cables
Surges IEC 61000-4-5
1.2/50 μs, 8/20 μs
1 kV line-to-line coupling
2 kV line-to-ground coupling
Radio-Frequency Electromagnetic
Field
IEC 61000-4-3
80 to 1000 MHz
10 V/m
80 % AM (1 kHz)
English
In order to comply with UL508C sta ndard, u se fuses UL ty pe J.
13259186