74 2604080000/03/08.2020Manual u-control
12 LEDindicatorsandtroubleshooting
Controller/indicator LED Status Recommended action
UC20-WL2000-IOT
Power LED PWR green: supply voltage present, rmware is running
System failure SF red: serious system failure Switch supply voltage off and on again and deploy
application again
Bus failure BF green: communication with modules OK
red: communication error with module or no modules
connected
Check whether modules are mounted correctly
Maintenance MT greenashingtwice: operating system is running
Controller status RUN off: no application deployed
green: application is deployed and running
Connection/active connection 1 L/A X1 off: no connection Check Ethernet cable
green: connection of controller connection 1 with an
additional eld device
green/yellowashing: data being exchanged on
connection 1
Connection/active connection 2 L/AX2 off: no connection Check Ethernet cable
green: connection of controller connection 2 with an
additional eld device established
green/yellowashing: data being exchanged on
connection 2
Input supply voltage 3.1 green: input current path supply voltage >18VDC
3.2 red: input current path supply voltage <18VDC Check supply voltage
3.4 red: internal fuse defective Replace the controller
Output supply voltage 4.1 green: output current path supply voltage >18VDC
4.2 red: output current path supply voltage <18VDC Check supply voltage
4.4 red: internal fuse defective Replace the controller