Installation and operating instruction
Gas burner WG20…/1-C LN
7 Commissioning
83240802 1/2020-01 La
38-96
Preset setting pressure
Only in conjunction with W-MF and gas connection pressure > 150mbar
The pre-pressure must be set to approx. 90 mbar.
Set FRS pressure regulator, see additional sheet (print No. 835109xx).
Pre-set setting pressure determined for ignition load 2 and full load 1 at multi-
function assembly.
1
2
Setting Factory presetting
1 Full load 7 mbar
2 Ignition load 4 mbar
The transition from ignition load to full load is carried out sliding.