STARTING YOUR GENERATOR
BEFORE STARTING THE GENERATOR
1. Verify that generator is outside on a dry, level surface with at
least two feet of clearance on all sides.
2. To maximize safety, check that the generator is properly
grounded (see “Ground the Generator”).
3. Check there is sufficient level of oil in the crankcase. Add oil
if necessary (see “Add / Check Oil”).
4. Make sure there is sufficient level of gasoline in the fuel tank.
Add fuel if necessary (see “Add / Check Fuel”).
5. Make sure all electrical devices are unplugged from the gen-
erator during ignition. Otherwise it will be difficult for the en-
gine to start.
STARTING THE GENERATOR
1. Turn the fuel valve (Fig. 9) to the ON position.
2. Move the choke lever (Fig. 10) to the CLOSE/START position
if the engine is cold. If the engine is warm, move the choke
lever to the OPEN/RUN position.
3. Turn the engine switch to the ON position.
4. Pull on the recoil starter handle slowly until a slight resistance is felt, then pull quickly to start the engine. Return
cord gently into the recoil starter. Never allow the cord to snap back.
If engine fails to start, repeat this step.
5. Once the engine has started, slowly move the choke lever all the way to the OPEN / RUN position.
6. Allow the engine to run for several minutes before attempting to connect any electrical devices. This allows the
generator to stabilize its speed and temperature. Follow the instructions in the "Using Your Generator" section for
properly connecting your electrical devices.
NOTE: In case you have had repeated failed attempts to start the engine, please consult the troubleshooting guide
before attempting to start the generator. If problems persist please call 1-(800) 232-1195, M-F 8-5 CST.
18
Fig. 9
Fig. 10