1
Blue 2” Heat Pump Thermostat
Heat Pump Installation and Operating Instructions
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
APPLICATIONS
1F89-0211 Thermostat
Model Programming Choices
1F89-0211 Non-Programmable
SPECIFICATIONS
Electrical Rating:
Battery Power or Hardwire ............................. 20 to 30 VAC, 50/60 Hz
Terminal Load ........................................................ 1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range ...................................................... 45° to 90°F (7° to 32°C)
Differential (Heat Pump) ........................................ Heat 1.2°F; Cool 1.2°F (adjustable)
Operating Ambient ................................................. 32° to +105°F (0° to +41°C)
Operating Humidity ................................................ 90% non-condensing max.
Shipping Temperature Range ................................ -40° to +150°F (-40° to +65°C)
Dimensions Thermostat ......................................... 3-3/4”H x 4-3/4”W x 1-1/2”D
PRECAUTIONS
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
Thermostat installation and all components of the
system shall conform to Class II (current limited)
circuits per the NEC code. Failure to do so could cause
a fire hazard.
WARNING
!
PART NO. 37-6997D
Replaces 37-6997C
1023
www.white-rodgers.com
www.emersonclimate.com
Index Page
Installation 2
Wiring Diagram 3
Thermostat Quick Reference 3
Installer Configuration Menu 4
Operation 5
Troubleshooting 6
THERMOSTAT APPLICATION GUIDE
Thermostat
Configuration
Options
Thermostat
Applications
Maximum
Stages
Heat/Cool
Heat Pump
Single Stage
Compressor
Single Stage Compressor
Heat Pump Systems – 1
Stage Aux/Emergency Heat
2/1

Questions and Answers

  • E
    Erin GreenAug 14, 2025
    How to troubleshoot White Rodgers 1F89-0211 with no heat, cool, or fan?
    • K
      Katherine PattersonAug 14, 2025
      Common reasons for a White Rodgers Thermostat not producing heat, cool, or fan output include a blown fuse or tripped circuit breaker, a furnace power switch set to OFF, or a furnace blower compartment door or panel that is loose or improperly installed. To resolve this, replace the fuse or reset the breaker, turn the furnace power switch to ON, and ensure the furnace blower compartment door or panel is correctly positioned to engage the safety interlock or door switch.
  • L
    Lindsey StevensAug 17, 2025
    How to calibrate White Rodgers 1F89-0211 if setting and thermometer disagree?
    • A
      Ashley DaughertyAug 17, 2025
      If your White Rodgers Thermostat setting and the thermometer reading don't match, you can adjust the thermometer setting by +/- 4 degrees in item 5 of the Configuration Menu. No other adjustments are possible.
  • M
    matthewbatesAug 20, 2025
    How to fix White Rodgers 1F89-0211 when furnace cycles too fast or slow?
    • A
      andrew70Aug 20, 2025
      If your White Rodgers Thermostat causes the furnace to cycle too fast or too slow, the thermostat's location or the heating system's size may be affecting the cycle rate. The cycle rate is controlled by Item 2 in the Configuration Menu. If you can't achieve an acceptable cycle rate using the FA (Fast) or SL (Slow) adjustment, contact a local service person for more advice.
  • E
    Eric HarringtonAug 25, 2025
    Why is my White Rodgers 1F89-0211 Thermostat not cooling?
    • R
      randycastilloAug 25, 2025
      If your White Rodgers Thermostat isn't cooling, make sure the System Switch is set to Cool and the setpoint is lower than the room temperature. Check that the thermostat and system wires are securely attached. Follow the same diagnostic steps as for a 'No Heat' condition, but set the thermostat to Cool and lower the setpoint below room temperature. Note that there may be a delay of up to five minutes before the thermostat clicks if the compressor lock-out option is enabled in the configuration menu (Item 4).
  • D
    Danny GainesAug 27, 2025
    Why is my White Rodgers 1F89-0211 Thermostat not heating?
    • S
      Stephanie GonzalezAug 27, 2025
      If your White Rodgers Thermostat isn't heating, first ensure the System Switch is set to Heat and the setpoint is higher than the room temperature. Verify that the thermostat and system wires are securely attached. To diagnose, set the System Switch to Heat and raise the setpoint above room temperature. Within five minutes, the thermostat should make a soft click, indicating it's likely working. If it doesn't click, try resetting it. If it still doesn't click after resetting, contact a service person or the place of purchase for a replacement. If it does click, contact the furnace manufacturer or a service person to check the heating system.
  • B
    bellkaraAug 31, 2025
    What to do if White Rodgers 1F89-0211 display is blank or keypad not responding?
    • M
      Misty MolinaAug 31, 2025
      If your White Rodgers Thermostat displays a blank screen or the keypad isn't responding, it might be due to a voltage spike or static discharge. Use the Reset Operation to resolve this.
  • J
    Jacob SpencerSep 3, 2025
    What to do if White Rodgers 1F89-0211 Thermostat heat, cool, or fan runs constantly?
    • V
      Veronica PattersonSep 3, 2025
      If your White Rodgers Thermostat is constantly running heat, cool, or fan, it could be due to a short in the wiring, the thermostat itself, or the Heat/Cool/Fan system. Another cause might be that the fan switch is set to 'Fan On'. Check all wire connections to ensure they are not shorted or touching, with no bare wire exposed under the terminal screws. Try resetting the thermostat. If the issue continues, have your system's manufacturer or a service person test the Heat/Cool system. If the system works correctly, consider replacing the thermostat.
  • D
    Donald BrowningSep 6, 2025
    How to adjust cooling cycle on White Rodgers 1F89-0211 Thermostat?
    • A
      Angela WilsonSep 6, 2025
      The cooling cycle rate for White Rodgers Thermostats is fixed and cannot be adjusted. Contact a local service person for suggestions.
  • C
    christina05Sep 10, 2025
    What does HP/SS switch mean on White Rodgers Thermostat?
    • E
      Emily HaleySep 10, 2025
      If your White Rodgers Thermostat has an HP/SS switch and the Configuration Menu also has a selection for HP or SS, it indicates an earlier version of the thermostat model. If there's a switch, ensure it's in the HP position for correct fan operation. If the selection is in the Configuration Menu, set it to HP.

Summary

PRECAUTIONS

WARNING

Safety warning regarding voltage exceeding limits and circuit compliance.

CAUTION

Safety caution to disconnect power before installation to prevent shock.

INSTALLATION

REMOVE OLD THERMOSTAT

Steps to safely remove the old thermostat and prepare for installation.

ATTACH THERMOSTAT BASE TO WALL

Instructions for mounting the thermostat base securely to the wall.

WIRING DIAGRAM

INSTALLER;CONFIGURATION MENU

ADVANCED CONFIGURATION OPTIONS

OPERATION

TROUBLESHOOTING

Reset and Common Problems

Reset procedure and troubleshooting for no heat/cool/fan, constant operation.

White Rodgers 1F89-0211 Specifications

General IconGeneral
TypeProgrammable Thermostat
DisplayDigital
Stages of Heating1
Stages of Cooling1
Display TypeLCD